1. Insulate chase.
2. Finish chase walls with dry wall 5/8 in. (16mm) Type X
face tape.
3. All dimensions are to finished walls and ceilings.
Figure 13.1 Sheetrocked Chase
WARNING
Fire Risk
Comply with all minimum clearances speci-
fied.
A minimum 1/2 in. (13mm) air clearance
must be maintained at the back and 1
in. (25mm) to the sides of the fireplace
assembly.
Chimney sections at any level require a 2
in. (51mm) minimum air space clearance
between the framing and chimney section.
D. Electrical Access and Wiring Diagram
NOTE: The manual override switch, rheostat
speed control and cover plate are supplied. You
will need to supply: 14-3 wire with ground; 14-2
wire with ground; standard wall mount junction
box; wire nuts.
1. Remove junction box cover plate on the
bottom right side of the fireplace.
2. Thread the 14-3 with ground wire through
the opening with the strain relief on the cover
plate.
3. Match colors to wire harness, (red to red,
white to white, etc) and secure with wire
nuts.
NOTE: Wiring for blowers must be done
before framed enclosure is completed.
If using a Heat Zone kit, it also must be
installed before enclosure is complete.
September 1, 2008
Fire Risk
Framing or finishing material used on the front
of, or in front of, the appliance closer than the
minimums listed, must be constructed entirely of
noncombustible materials (i.e., steel studs, concrete
board, etc.).
14-3 w/ground
Match colors to wire
harness (red to red,
white to white, etc) and
secure with a wire nut
Power to the Fireplace
Snap Disc
bypass switch
Figure 13.2 Fan Wiring Diagram
433-1390G
7100FP EPA Woodburning Fireplace
WARNING
Fire Risk
Do not apply combustible finishing materials
over any part of the front of this fireplace.
The metal fireplace face may only be
covered with noncombustible materials
such as ceramic tile, brick, or stone.
Do not cover or block any cooling air
slots.
The decorative fascia must be removable
for future serviceability of the Automatic
Combustion Control.
WARNING
Maintain clearances.
Use only non-combustible material below
standoffs, material such as cement board
is acceptable.
Standard wall mount with
Junction Box
14-2 w/ground
WIRE NUT
WHITE
WHITE
GREEN
RED
BLACK
Incoming Power
(110V)
Page 13