7100FP EPA Woodburning Fireplace
C. Using Offsets/Returns
To bypass any overhead obstructions, the chimney may be
offset using an offset/return.
An offset and return may be attached together or a chimney
section(s) may be used between an offset and return.
Perform the following steps to determine the correct chim-
ney component combination for your particular installation:
WARNING
Fire Risk
DO NOT combine offsets to create an offset
greater than 30° from vertical.
Draft will be restricted.
Table 22.1
Part SL315
Part SL315
15°
30°
A
B
A
1-5/8"
13-3/8"
3-7/8"
2-7/8"
17-3/4"
6-1/4"
-
-
8-5/8"
4-1/2"
23-5/8"
9-1/4"
-
-
11-5/8"
6"
29-3/8"
12-1/4"
7-1/4"
34"
14-5/8"
-
-
15-1/4"
-
-
17-5/8"
-
-
20-5/8"
10-5/8"
46-3/4"
21-1/4"
11-7/8"
51-3/8"
23-5/8"
-
-
26-5/8"
13-3/4"
58-3/8"
27-1/4"
15"
63"
29-5/8"
16-1/2"
68-3/4"
32-5/8"
18"
74-5/8"
35-5/8"
-
-
38-5/8"
-
-
41"
22-3/4"
91-7/8"
44-5/8"
24"
96-1/2"
47"
25"
103-1/2" 50-5/8"
Page 22
SL306
SL312
SL318
B
14-1/2"
-
-
18-5/8"
1
-
22-3/4"
2
-
23-3/4"
-
1
27-7/8"
1
1
29"
-
-
33"
-
2
34-1/8"
-
-
38-1/4"
1
-
43-1/2"
-
-
44-5/8"
-
-
48-3/8"
1
-
53-7/8"
-
-
55-3/4"
-
-
59"
1
-
64-1/4"
-
1
69-1/2"
-
-
74-5/8"
-
-
78-3/4"
1
-
85"
-
-
89-1/8"
1
-
95-1/2"
-
-
Measure how far the chimney needs to be shifted to enable
it to avoid the overhead obstacle. See Figure 22.2. Use
dimension "A" to determine chimney section required to
achieve the needed shift.
After determining the offset dimension, refer to Table 22.1
and find the "A" dimension closest to but not less than the
distance of shift needed for your installation.
The "B" dimension that coincides with the "A" dimension
represents the required vertical clearance that is needed
to complete the offset and return.
Read across the chart and find the number of chimney
sections required and the model number of those particular
chimney parts.
Whenever the chimney penetrates a floor/ceiling, a ceiling
firestop must be installed.
The effective height of the fireplace assembly is measured
from the base of the fireplace.
SL324
SL336
SL348
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
-
-
-
-
-
-
-
2
1
-
-
-
1
-
-
-
-
-
-
-
-
1
-
-
-
1
-
-
2
-
-
-
-
-
-
-
-
-
1
-
-
-
1
1
-
-
1
-
1
-
1
-
1
-
1
-
-
1
1
-
-
1
1
-
-
-
2
433-1390G
Example:
Your "A" dimension from Figure 22.2 is
14 1/2 in. (368 mm). Using Table 22.1
the dimension closest to, but not less
than 14 1/2 in. (368 mm) is 14 1/2 in.
(368 mm) using a 30° offset/return. It is
then determined from the table that you
would need 34 1/8 in. (867 mm) (Dimen-
sion "B") between the offset and return.
The chimney component that best fits
your application is one SL324.
A
B
1-1/4 in. (32 mm)
OVERLAP
Figure 22.2 Chimney Offset/
Return