Table of Contents

Advertisement

4.
If rack installed, slide the server completely out from the rack. See
the Rack" (page
5.
Remove the top cover. See
6.
Disconnect the internal USB cable from the connector on the core I/O board.
7.
Disconnect the SAS cables attached to the SAS core I/O card in PCI slot 1.
CAUTION:
and sockets are clearly marked with the correct channel. When reconnecting these cables,
match each cable with the appropriate socket on the SAS core I/O card. If the cables are
mismatched, the server will not reboot.
8.
Slide the server completely back into the rack.
9.
Open the cable management arm wide enough to slide the I/O board out the rear of the
rack.
10. Disconnect all external cabling attached to ports at the rear of the chassis.
1 1. Press in on the retention levers to unlock the I/O board assembly extraction handles
12. Pull the I/O board assembly extraction handles outward to unplug the I/O board assembly
from the socket on the midplane board.
13. Slide the I/O board assembly all the way out the rear of the chassis
NOTE:
224 Removing and Replacing Server Components
176).
"Removing the Top Cover" (page
When disconnecting the SAS cables, note the labeling on the cables. Both cables
The I/O board assembly is large. Use care when lifting it out of the server chassis.
"Extending the Server from
178).
(Figure
(Figure
77).
77).