Before Wiring TrueSTEAM
TrueSTEAM wiring is different from evaporative pad humidifier wiring, in addition to solenoid water valve
actuation, TrueSTEAM can monitor system power and regulate system fan operation.
Using the DiP Switches
The wiring features are configured by DiP settings, which are described
under the TrueSTEAM cover.
STEP ONE: Remove
the TrueSTEAM
Cover
Loosen the cover screw.
Slide cover out from front.
With the cover removed, you will see six DIP switches
to the left of the user interface panel. This manual
refers to DIPs 1-6 from left to right.
STEP TWO: Understand
the DiP Switches
OR
Off
®®
DIPS 1 and 2 are used for maintenance.
DIP 1 and DIP 2: Together, these two DIPs specify
how often the automatic flush cycle is performed. See
"Set the Automatic Flush Cycle Timing" on page 13.