Honeywell TrueSTEAM HM506 Installation Manual page 35

Hide thumbs Also See for TrueSTEAM HM506:
Table of Contents

Advertisement

Available languages

Available languages

No. of
Fault Description
Auto-Recoverable?
Steps to Fix
Service
LED
(Performed
Only By Professional
HVAC Technician)
Blinks
17
Power to the wireless
Yes, system will
1. Verify wiring between TrueSTEAM and the wireless adapter.
adapter overloaded,
return to "Ready"
2. Ensure DIP switches are set correctly. (DIP 3 up. Also DIP 4 up
if fault no longer
if TrueSTEAM R and C aren't wired.)
exists in one hour.
3. If the fault persists, replace the wireless adapter.
18
Wireless
Yes, system will
1. Verify wiring between TrueSTEAM and the wireless adapter.
communication
return to "Ready"
2. Verify the Prestige control is operating correctly.
from wireless
after one minute.
3. If the fault persists, replace wireless adapter and re-enroll
adapter failed,
connection to Prestige.
Cleaning
Required
light
is on.
Tank was slow to
drain during last
automatic flush cycle
or 12-month cleaning
interval time
has expired.
N/A
Follow the tank cleaning steps. See "Manua/C/eaning
Cyc/e"
on page 24.
TrueSTEAMHumidification System 69-2285EF--01
33