ELECTRODE STEAM HUMIDIFIER
MOUNTING
Mounting Procedure
1. The HM700 humidifier is wall mounted using a key-
hole located on the back of the humidifier.
2. Use #8 x 2 in. (5 cm) screws mounted into 2x4
studs or better if there is drywall or other spacers.
Two screws are needed, one for hanging the unit
and one for securing it so it will not lift off the
keyhole.
3. Install the top screw so that 1/4 in. (6 mm) is
exposed. Raise the unit and place the screw head
through the keyhole.
4. Make sure the unit is level and then insert and
tighten the second screw through the bottom hole.
Tighten the top screw.
5-95%
Mount humidifier
24 in.(61 cm)
level
min. height
Fig. 1. Mounting.
Mounting Requirements
Honeywell does not accept responsibility for installation
code violations.
1. Install as close as possible to the steam distributor.
2. Minimize the use of turn or bends in the steam line
as much as feasibly possible.
3. Mount on a suitable wall or vertical surface. Do not
sit the on the floor, where freezing can occur, or on
vibrating surfaces.
4. Allow clearances for plumbing and electrical con-
nections. Consult local and national codes prior to
final location and installation.
5. Install only in areas with ambient temperature
41-104 °F (5-40 °C), and relative humidity 5-95 %
(noncondensing).
6. When possible, mount the HM700 humidifier at a
height convenient for servicing.
As close as
possible to steam
distributor
36 in. (92 cm)
duct model
min. front clearance
QUICK START GUIDE
33-00162-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell HM700A1000

  • Page 1 ELECTRODE STEAM HUMIDIFIER QUICK START GUIDE MOUNTING Mounting Requirements Honeywell does not accept responsibility for installation code violations. Mounting Procedure 1. The HM700 humidifier is wall mounted using a key- 1. Install as close as possible to the steam distributor.
  • Page 2: Water Supply Requirements

    Water Supply Requirements Drain Line Requirements 1. Use 7/8 in. copper. Do not use PVC. Honeywell does not accept responsibility for installation code violations. All drain and fill line connections should 2. Install an air gap within three feet of the humidifier.
  • Page 3: Install Requirements

    Fig. 3. Primary power connection. NOTES: — Honeywell requires the use of a GFI circuit on this device to protect the homeowner from electrical shock. — When installed correctly, the green wire should be removed from the drain valve. The green wire comes pre-installed from the factory to protect the homeowner in case of an improper installation or when it is not possible to retrofit a GFI circuit.
  • Page 4: Steam Distribution

    (3.5) (0.7) The use of steam line other than copper, stainless steel tube or Honeywell supplied steam line will void the warranty and may adversely affect the operation of the humidifier. When using copper or stainless steel tubing (other than the supplied tubing), insulation is recommended due to high temperature safety as well as reduced condensate.
  • Page 5: Installation Check

    HM700A1000 INSTALLATION CHECK Before turning on power to the HM700, inspect the installation to ensure that it was carried out correctly. Air Proving (optional) High Limit In series between On/Off terminals 1 and 2. Bend, or other (optional) Jumper between...
  • Page 6 HM700A1000 33-00162—01...
  • Page 7 HM700A1000 33-00162—01...
  • Page 8 1-800-468-1502 or 1-800-814-9452 Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2015 Honeywell International Inc. 33-00162—01 M.S. 11-15 customer.honeywell.com Printed in United States...

Table of Contents