taBle 2. aDvanceD conFIGUratIon servIce menUs (cont.)
menU
FeatUre
System Mode Enable
360
Economizer/Outside
370
Air Damper Control
Minimum Deadband
380
Adjustment
Restart Occupancy
388
Sensor Count when
not-enabled.
Pre-Occupancy Purge
390
Adaptive
391
Pre-Conditioning
Schedule (APCS)
Persistence
392
(for APCS)
Maximum Override
395
Time Limit
School Schedule
396
Default Occupied
Duration When
Enabled
School Schedule
397
Default Occupied
Duration When
Disabled
School Schedule Max.
398
Occupied Duration
When Enabled
School Schedule Max.
399
Occupied Duration
When Disabled
Cycles Per Hour
400
(CPH) Cooling
Stage 1
Cycles Per Hour
410
(CPH) Cooling
Stage 2
Cycles Per Hour
420
(CPH) Heating
Stage 1
Cycles Per Hour
430
(CPH) Heating
Stage 2
© COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED.
oPtIons
stD.moDel
DescrIPtIon / comments
DeFaUlt
0-3
1
Allows ability to determine which system modes the occupant can select.
0 =
1 =
2 =
3 =
0-4
0
0 =
1 =
2 =
3 =
4 =
3-10°F,
3°F
Select a changeover deadband value to prevent short cycling between heating and cooling modes.
1.5-5°C
The value is adjustable to meet various HVAC system requirements.
0-2
0
Providing an "occupied" input signal behaves the same as pressing the Teacher key. note: In the event that
the teacher button and the occupancy sensor are not in the same state, the Teacher key takes precedence.
0 =
1 =
2 =
0-3 hours
0 hours
Select to energize fan for selected number of hours (0-3) prior to all occupied events.
0-1
0
Enables adaptive pre-conditioning schedule (and requires input by user or occupancy sensor after enabled).
0 =
1 =
1-4
2
Selects the number of weeks that an APCS event shall remain in the schedule.
1 = Event will be removed from the schedule the first time that it does not recur.
0=Time until
3
Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum
next event;
amount of time as defined in this Service Menu.
or
0 =
1-4 hours
1 =
2 =
3 =
4 =
0; 0:15; 0:30;
99 (max.)
Sets the default occupied duration,when Teacher key is pressed, during School Schedule "enabled" period.
1; 2; 3; 4; 6;
0 = Occupied duration not available to teacher. Occupied duration set to "Max occupied time when
8; 99
99 = Occupied duration is available to teacher; defaults to "Max occupied duration when enabled" setting.
0:15; 0:30; 1;
0:15
Sets the default occupied duration, when Teacher key is pressed, in School Schedule "Disabled" period.
2; 3; 4; 6; 8
0:15; 0:30;
1
Sets the maximum occupied duration that the user can enter during the "enabled" schedule period.
1; 2; 3; 4; 6;
99 = Thermostat can be set to remain occupied until the end of the Enabled period.
8; 99
0; 0:15; 0:30;
0:15
Sets the maximum occupied duration that the user can enter during the "Disabled" schedule period
1; 2; 3; 4;
0 =
6; 8
0-6 CPH
3 CPH
Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for Stage 1
cooling.
0-6 CPH
3 CPH
Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for Stage 2
cooling.
0-12 CPH
5 CPH
Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for Stage 1
heating.
0-12 CPH
5 CPH
Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for Stage 2
heating.
OFF, Auto
OFF, Heat, Cool, Auto
OFF, Heat, Cool
Heat, Cool, Auto
Off
Time Based Output
Economizer
Continuous Outside Air Damper
Cycled Outside Air Damper (Note: Cycles on demand if CO
No occupancy sensor installed in system.
Status changes to unoccupied after time set in occupied time setting runs out, regardless of
occupancy sensor input.
Status remains as occupied as long as occupancy sensor indicates room is occupied.
Disabled
Enabled; state learns pre-purge and recovery schedule.
Remainder of time until the next scheduled event.
1 Hour
2 Hours
3 Hours
4 Hours
enabled" setting.
Thermostat will not become occupied in Disabled schedule period.
7
Sensor is applied and configured.)
2
P/N 70568 3220-2287 REV 00