wIre Peco oUtDoor remote sensor
1. Wire the PECO Outdoor Remote Sensor to Terminal S1 and Sensor Common (SC) on
the thermostat wallplate (see Fig. 27).
note: See Table 1 for terminal designations for the Outdoor Remote Sensor.
2. Assure that Step 6 (previous section) is complete and the PECO Outdoor Remote
Sensor is secure.
3. Plug the wiring passage using non-hardening caulk or putty.
Figure 27.
Wire PECO Remote
Outdoor Sensor to
Performance PRO
wallplate, Terminal S1, SC.
wiring passage
4. Go to Service Menu 170, select from options 2-5, Outdoor Remote Sensor (see Fig.28).
Figure 28.
Service
Menu 170
allows the
user to
enable the
Outdoor
Remote
Sensor.
economIZer / tIme-oF-DaY (toD) loGIc
Allow the outdoor or indoor temperature sensor to absorb the air for a minimum of fi ve
minutes before taking a reading. See Service Menu 370, which controls Economizer/
Outside air damper behavior. Table 6 shows the Economizer/TOD behaviors of available
settings (Options include 0-4; 0 = OFF, which disables the Economizer function).
taBle 6.
effective
cooling
370 = 1 (toD)
occupancy
Demand
Occupied
N/A
ON Continuously
YES
OFF
Unoccupied
NO
OFF
Override
NA
ON Continuously
Demand
system
370 =3 (continuous oa)
mode
Heating
Heat
ON Continuously
Cooling
Cool
ON Continuously
None
OFF
OFF
Heating or
Auto
ON Continuously
Cooling
© COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED.
Terminal SC
Terminal S1
economizer output
370 = 2 (economizer)
ON Continuously
ON (Cycles with demand)
OFF
ON Continuously
370 = 4 (cycled oa)
ON (Cycles with demand)
ON (Cycles with demand)
OFF
ON (Cycles with demand)
heat PUmP temPeratUre lockoUts
note: heat Pump compressor lockouts (shown below) are only available if an
outdoor temperature sensor is applied and confi gured (see table 1).
The options available in Service Menu 140 (below) are dependent on the selected System
Type, Service Menu 110.
DUal FUel heat PUmP anD remote oUtDoor remote sensor
In this operation, there is no external fossil fuel kit (dual fuel kit) installed; the thermostat
controls this function:
1. Choose the correct heat pump application in Service Menu 110, System Type.
2. Choose Outdoor Temperature Sensor (Options 3 or 5) for Control Option in Service
Menu 170, Remote Sensor.
3. Go to Service Menu 140, Auxiliary Heat, and choose "1."
4. Choose an appropriate temperature balance point in Service Menu 180, Heat Pump
Compressor Lockout.
Operation in Heat Mode Above Balance Point (Outdoor Temperature)
When the outdoor temperature is above the selected balance point temperature (Service
Menu 180), only the compressor operates and the fan (G Terminal) energizes when the
thermostat calls for heat.
Operation in Heat Mode Below Balance Point (Outdoor Temperature)
When the outdoor temperature is below the selected balance point temperature (Service
Menu 180), only the Fossil Fuel (auxiliary heat) operates and the fan (G Terminal) does not
energize when the thermostat calls for heat.
FossIl FUel aUXIlIarY heat
If Service Menu 140 is set to "1" (fossil fuel Auxiliary Heat), the lockout control is as
follows:
Only Compressor Operates
40° F
Only Auxiliary Heat Operates
heat PUmP wIth aUXIlIarY (BackUP) heat anD oUtDoor

temPeratUre sensor

1. Choose the correct heat pump application in Service Menu 110, System Type.
2. In Service Menu 170, Remote Sensor, Choose Outdoor Temperature Sensor (Options
3/5) for Control Option.
3. Go to Service Menu 140, Auxiliary Heat, and choose "0."
4. Choose appropriate balance point in the Service Menu 180, Heat Pump Compressor
Lockout.
5. Choose Auxiliary Lockout Temperature in Service Menu 190, Heat Pump Auxiliary
Lockout.
note: there is a minimum 5°F deadband between compressor and auxiliary heat
lockout temperatures.
Operation
When the outdoor temperature is:
• Below the Heat Pump Compressor Lockout Temperature, only the Auxiliary Heat
operates.
• Above the Heat Pump Auxiliary Lockout Temperature, only the Compressor
operates.
• Between the two temperatures, both the Compressor and Auxiliary Heat operate.
electrIc aUXIlIarY heat
If Service Menu 140 is set to "0" (electric Auxiliary Heat) the lockout control is as follows:
Only Compressor Operates
40° F
Both Compressor & Auxiliary Heat
Operate
20° F
Only Auxiliary Heat Operates
13
Compressor
Lockout
Temperature
Auxiliary Lockout
Temperature
Compressor Lockout
Temperature
P/N 70568 3220-2287 REV 00