taBle 2. aDvanceD conFIGUratIon servIce menUs (cont.)
menU
FeatUre
Enable UV Filter
232
Timer
UV Filter
233
Timer Hours
Number of Program
240
Periods
Clock format
12 or 24 Hours
250
Temperature Format
260
(°F or °C)
Fan Off Delay Heat
270
Fan Off Delay Cool
280
Range Low
290
Range High
300
Teacher Key Heat
302
Setpoint Increase
Teacher Key Heat
303
Setpoint Decrease
Teacher Key Cool
304
Setpoint Increase
Teacher Key Cool
305
Setpoint Decrease
Setback Low
Off; 50-82°F or
310
Setback High
Off; 58-90°F or
320
Zone Temp Offset
330
Keypad Lockout
340
Enable Pin Access
341
Set PIN Access
342
Code
Fan Mode
350
Enable
© COPYRIGHT 2011 PECO, INC. ALL RIGHTS RESERVED.
oPtIons
stD.moDel
DeFaUlt
0-1
0
0-250
120
(hundreds of hours)
2; 4 events
4
12
0,1
1
0-99 Seconds
0
0-99 Seconds
0
50-90 °F or
50°F (10°C)
10-32°C
50-90 °F or
90°F (32°C)
10-32°C
0-10 °F
3 °F
0-10 °F
3 °F
0-10 °F
3 °F
0-10 °F
3 °F
55°F (13°C)
11-27°C
90°F (32°C)
11-32°C
+/-9°F or +/-
0°F (18 °C)
4.5°C
0-3
0
0,1
0
000-999
000
1-3
3
DescrIPtIon / comments
Activates the UV Filter Timer. UV Filter timer measures the on-time for Fan output in service of heat,
cool, humidify, or dehumidify (Note: UV lamp life varies by manufacturer. PECO is not responsible for
lamp life nor for UV filter.)
0 =
UV timer disabled
1 =
UV timer enabled
Reports UV Filter Timer in hundreds of hours. (Default: Number of hours remaining 120 = 12,000
hours). Service Indicator (wrench) is shown in Default Display when timer expires. When the UV Filter
Timer expires, in Home Display the clock area alternates between the time display and "F 01."
2 =
2 events per day
4 =
4 events per day
12 = 12-hour clock mode
24 = 24-hour clock mode
0 =
Celsius
1 =
Fahrenheit
Select the amount of time (in seconds) that the fan will run after the thermostat heat outputs are turned
off.
Select the amount of time (in seconds) that the fan will run after the thermostat
off.
Choose the lowest selectable temperature setpoint value. Only available with Performance PRO
settings (see SM 100).
Choose the highest selectable temperature setpoint value. Only available with Performance PRO
settings (see SM 100).
Sets number of degrees that teacher can increase the temperature above the Occupied Heat Setpoint.
Sets number of degrees that teacher can decrease the temperature below the Occupied Heat Setpoint.
Sets number of degrees that teacher can increase the temperature above the Occupied Cool Setpoint.
Sets number of degrees that teacher can decrease the temperature below the Occupied Cool Setpoint.
Select the heat setpoint for setback mode. Only available with Performance PRO settings (see SM 100).
0 =
Off
50-82°F (11-27°C)
Select the cool setpoint for setback mode. Only available with Performance PRO standard settings
(see SM 100).
0 =
Off
58-90°F (11-32°C)
Adjusts the displayed value; may differ from actual zone temperature.
Restricts access to certain features of device; Service Menu still available if enabled.
0 =
No keypad lockout (Default)
1 =
Disables Schedule and System keys
2 =
Disables Schedule, System, and Fan keys
3 =
Disables all keys
Applies a 3 digit access code to enter Service Menu 342
0 =
Disable
1 =
Enable
Choose a 3-digit code.
1 =
ON: Fan is turned on regardless of demand.
2 =
Auto: Fan is turned on according to heating or cooling demand.
3 =
ON or Auto: Allows occupant to select either 1 or 2 above.
6
cool
outputs are turned
P/N 70568 3220-2287 REV 00