NHTC/PC Pre-Start Up Checklist
Unit Serial #: _________________ Tag: _______________
Unit type: _______ __________
Cylinder type:
Water Quality:
Well water City water Softened water
Humidifier Mounting: (Clearances around the unit Acceptable Obstruction)
Level Front/Side Clearance
Steam Line(s):
Slope up (min 2 in/ft).
Diameter / Size
Low point condensate traps
Type of Insulation
Condensate Line(s):
P Trap min 6 in or duct press + 2in
Water Line:
1/2 in to within 4ft of unit
Drain Line:
Air gap within 3 ft of the unit
Cylinder:
Seated in drain valve and secured
Wiring:
Wiring connections and connectors secured
Controls:
Control Location
High Limit Location
Power:
Voltage, amp, fuse per Spec Label:
Disconnect switch located close to humidifier
Panel Number
Inspected by:
Company:
39 | Start Up
Voltage: ________V/_____ph Steam output: ______lb/hr
Customer/Job:
Slope down (min 0.500 in/ft)
Material
No Hose Kinks / Restrictions
P Trap min 12 in drop
Water pressure: 30-80 psig
Diameter / Size
yes
yes
Control to Terminal 4
High Limit to terminal 5
yes
yes
Date of inspection: ______/_______/______
Address:
no
no
no
no