Nortec SETC/P Pre-Start Up Checklist
Unit Serial #:
Unit type:
Customer/Job:
Water Quality:
Potable (0-12 grains/gal, 0-14 ppm Silica, 0-25 ppm Chlorides) RO DI
Humidifier Mounting: (Clearances around the unit Acceptable Obstruction)
Level Front/Side Clearance
Steam Line(s):
Slope up (min 2 in/ft).
Diameter / Size
Low point condensate traps
Insulated
Condensate Line(s):
P Trap min 8 in. (20 cm) plus duct static pressure P Trap min 12 in drop
Water Line:
Can provide required flow
Drain Line:
Air gap within 3 ft of the unit
Auxiliary drain connected with shut off valve
Boiler Steam
Boiler Pressure
15 psi relief valve if med/high press boiler
Actuator closes and opens CV valve fully
Condensate return Gravity feed or pump
Wiring:
Wiring connections and connectors secured
Controls:
Control Location
High Limit Location
Power:
Voltage, amp, fuse per Spec Label:
Disconnect switch located close to humidifier
Inspected by:
Company:
41 | Start Up
Tag:
Voltage:
V/
Address:
Anchored (if on stand)
psi
yes
Date of inspection:
ph Steam output:
Slope down (min 0.500 in/ft)
Material
No Hose Kinks / Restrictions
Type of Insulation
Water pressure: 30-80 psig
Diameter / Size
Pressure to humidifier
Design pressure at CV valve
no
Control to Terminal 4
High Limit to terminal 5
yes
no
yes
no
/
lb/hr
psi
/