Options and Accessories

Note:
For installation of options and accessories follow the instructions that are provided
with them.

Built On or Remote Blower Pack

Built on and remote blower packs are available for the NHTC/PC for applications where steam
for humidification must be introduced directly into the space being humidified. For instructions
on installing the remote blower pack refer to the installation instructions supplied with it. The
steam line and condensate return instructions provided in this manual are also applicable to
remote mounted blower packs.
Steam Line
Installation of an NHTC/PC with a built on blower pack is identical to installation of an NHTC/PC
without a blower pack. The steam line, condensate return and wiring connections to the blower
pack have been done at the factory.

Fill Cup Extension

For installations where duct static pressure exceeds 6 inches a fill cup extension kit is required.
The provides a bracket and hoses for mounting the fill cup above the humidifier. The fill cup
extension kit may be required if water runs to drain while the humidifier is filling. See chapter
on troubleshooting for more information on diagnosing fill problems.
29 | Installation
Figure 30: Remote Mounted Blower Pack
Blower Pack
Condensate Drain
"P" Trap