NHTC/PC Maintenance Checklist
Model #: _________________
Serial #: _________________
Cylinder #:
Cylinder / System Check
W19 Cylinder Spent
(If software displays W19 or E19 then cylinder must be replaced)
Yellow LED On with W12- Sensor On Warning.
(If Yellow LED is On with W12 and cylinder is not new then cylinder will have to be replaced soon.)
Other warnings or Faults shown in display?
(See Troubleshooting Chapter for actions to address warnings and faults if present
Replace Cylinder
Cylinder drained.
Disconnect open, On/Off switch to Off, water shut off valve closed, door removed.
Cylinder removed
Drain valve removed / cleaned / new O-Ring
Drain valve installed / ground wire attached.
New Cylinder Installed and hose clamps tight.
Cylinder plug colors match cylinder dots.
Cylinder plugs snug and in good condition.
High Water Sensor plug snug and in good condition.
Electrical wiring not loose and in good condition,
Steam hoses and steam lines in good condition / No kinks in hose,
No Signs of water leaking around humidifier, steam line, condensate returns,
Door replaced, water shut off valve opened, On/Off switch to On, Disconnect Closed
"Reset Cylinder" in Software, (Password 0335, Service Level)
Inspected by:
Company:
Tag: ________
E19 Cylinder Spent
No
Yes
New cylinder model #
(Should be same as removed cylinder)
Date of inspection: _______/_______/______
)
Maintenance and Servicing | 66