Configuring Battery Settings; Configuring The Ups For Ebms - Eaton 9130 UPS User Manual

Powerware series 700–3000 va ups
Table of Contents

Advertisement

Configuring Battery Settings

Eaton
®
9130 UPS (700–3000 VA) User's Guide
Set the UPS for the number of EBMs installed, whether to run automatic
battery tests, and automatic restart configuration.

Configuring the UPS for EBMs

To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
Press any button on the front panel display to activate the menu
options, then select SETTINGS, USER SETTINGS, and NUMBER OF
BATTERY STRINGS.
2.
Use the
or buttons to select the number of battery strings
according to your UPS configuration:
All UPS and EBM Cabinets
UPS only (internal batteries)
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
UPS + 4 EBMs
NOTE If 0 is selected, no batteries are connected and all battery-related
alarms are disabled.
NOTE The UPS contains one battery string; each EBM contains two battery
strings.
3.
Press the
button to save the setting.
ESC
4.
Press the
button until the start screen appears.
Number of Battery Strings
S
164201718 Rev 3 www.eaton.com/powerquality
OPERATION
1 (default)
3
5
7
9
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9130

Table of Contents