Eaton 9130 UPS User Manual page 49

Powerware series 700–3000 va ups
Table of Contents

Advertisement

Table 3. User Settings (continued)
Description
Frequency Converter
Overload Alarm Level
Transfer to Bypass When Overload*
Power Strategy
Automatic Start Delay
Automatic on Battery Shutdown
Start on Battery
NOTE Utility must be present and
output enabled at initial UPS startup.
Energy Saving Mode
Remote Shutdown Delay
Delayed Shutdown Delay
Behavior on Rectifier Input Loss
NOTE Available only in >3000 VA
UPSs with separate supply sources
for the rectifier and bypass inputs.
On Battery Notice Delay
* See "Configuring Bypass Settings" on page 48.
Eaton
®
9130 UPS (700–3000 VA) User's Guide
Available Settings
[Enabled] [Disabled]
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all
bypass-related alarms disabled.
[10%] [20%] [30%] ... [100%]
These values affect alarm level only, not UPS
operation such as transfers or shutdown.
[Immediate] [After Delay]
If Immediate, transfer occurs at load >102%.
If After Delay, transfer occurs according to
Table 19 on page 84.
[Normal] [High Efficiency]
See "Setting Power Strategy" on page 48.
[Disabled] [No Delay] [1s] [2s]...[32767s]
If Disabled, automatic restart is not allowed.
See "Configuring Load Segments" on page 49.
[Disabled] [No Delay] [1s] [2s]...[32767s]
Shutdown cancels if utility returns before the
delay expires. See "Configuring Load
Segments" on page 49.
[Enabled] [Disabled]
After initial startup, battery voltage must
exceed 2.10 volts per cell to start on battery.
[Disabled] [50W] [100W] ... [1000W]
UPS output is turned off if the UPS is on
battery and output power is below the
selected level.
[No Delay] [1s] [2s]...[10800s]
[No Delay] [1s] [2s]...[10800s]
[Prefer Battery] [Prefer Bypass]
If Prefer Bypass, upon loss the UPS will
transfer to bypass in 3 seconds and remain as
long as bypass is available.
[0] [1s] [2s]...[99s]
S
164201718 Rev 3 www.eaton.com/powerquality
OPERATION
Default Setting
Disabled
100%
Generates the Output Overload
alarm at the set level.
Immediate
Normal
Load Segment 1: No Delay
Load Segment 2: No Delay
Load Segment 1: Disabled
Load Segment 2: Disabled
Enabled
Disabled
No Delay
120s
Prefer Battery
5s
41