Eaton 9130 UPS User Manual page 95

Powerware series 700–3000 va ups
Table of Contents

Advertisement

Table 22. Environmental and Safety (All Models)
Surge Suppression
EMC Certifications
EMC (Emissions)
Safety Conformance
Agency Markings
Operating Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Audible Noise
Leakage Current
Eaton
®
9130 UPS (700–3000 VA) User's Guide
120 Vac Models
ANSI C62.41 Category B3
(6 KV Ring and Combination)
<1500 VA: FCC Class B, VCCI Class B,
EN 55022 Class B
>2000 VA: FCC Class A, VCCI Class A,
EN 55022 Class A
IEC 62040-2:ed2:2005 / EN 62040-2:2006
UL 1778, IEC 62040-1-1, IEC 60950-1
0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude
NOTE Thermal protection switches load to Bypass in case of overheating.
-20°C to 40°C (-4°F to 104°F) with batteries
-25°C to 55°C (-13°F to 131°F) without batteries
-25°C to 55°C (-13°F to 131°F)
Up to 3,000 meters (9,843 ft) above sea level
Up to 10,000 meters (32,808 ft) above sea level
S
164201718 Rev 3 www.eaton.com/powerquality
208/230/240 Vac Models
EN 61000-4-2, Level 3
EN 61000-4-3, Level 2
EN 61000-4-4, Level 2 (also on signal ports)
EN 6100-4-5, Level 3 Criteria A
EN 61000-4-6, Level 2
EN 61000-4-8, Level 2
CE per IEC/EN 62040-2,
Emissions: Category C1,
Immunity: Category C2
CE, UL, CUL, NOM
5–90% noncondensing
<50 dBA at 1 meter typical
<1.5 mA
SPECIFICATIONS
EN 61000-2-2
EN 6100-4-11
87