A. Heat Zone Kit (Optional)
The Heat-Zone accessory kit conveys warm air from the fire-
place through air duct(s) to remote locations in the same room
or other rooms of the building. You may install 1 or 2 Heat-Zone
kits on the fireplace. Follow the instructions that is supplied with
the kit. Installation of this kit MUST be performed by a quali-
fied service technician. If any parts are missing or damaged,
contact your local dealer before starting installation. DO NOT
install a damaged kit.
This kit is tested and safe when installed in accordance with
this installation manual. It is your responsibility to read all
instructions before starting installation and to follow these
instructions carefully during installations.
Installation of this kit MUST by performed by a qualified ser-
vice technician.
The Heat-Zone® Wood kit is carefully engineered and must
be installed only as specified. If you modify it or any of its
components you will void the warranty and you may possibly
cause a fire hazard. Installation must be done according to
applicable local, state, provincial and/or national codes.
Plan the location of the fireplace and warm air duct run(s).
Figure 11.1
Minimum Clearances to Combustibles
4/12
Possible Air Duct Runs / Locations
12 in. (305mm) minimum clearance
from register to ceiling
Wall Register
Two Duct Kits
DUCT RUN REQUIREMENTS
MAXIMUM Duct Run = 40-ft. (12m)
MINIMUM Duct Run = 36 in. (914mm)
DUCTING MATERIAL
6 in. (152mm) B-Vent Only
DO NOT DUCT into existing furnace plenum
MINIMUM CLEARANCE TO COMBUSTIBLES
1 in. (25mm) from the B-Vent
1/2 in. (13mm) from top & bottom of outlet box
0 in. (0mm) from the sides of outlet box
12 in. (305mm) from wall register to ceiling
(See Figure 11.1).
Caution! ALL wiring should be done by a qualified electri-
cian and shall be in compliance with local codes and with
the National Electric Code NFPA/NEC No. 70-current.
CSC22.1 Canadian Electric Code.
Ceiling Register
Floor Register
433-1390K
Ceiling Register
Page 60