Danfoss DHP-AX User Manual page 29

Table of Contents

Advertisement

5.1.6
Sub-menu DEFROST
In the "DEFROST" menu it is possible to view miscel-
laneous information about defrosting the outdoor
unit and also possible to make adjustments.
Menu text
DEFROSTS
BETW. 2 DEFR
TIME LAST DEFR
DEFROST CURVE
MANUAL DEFR
Description
Total number of defrosts carried out since
installation, i.e. the number not reset.
The operating time of the compressor in
minutes between the 2 last defrosts.
The operating time of the compressor in
minutes since last defrost. Reset after a
defrost is completed.
Here, the angle of the defrost curve can
be changed using the right-hand arrow
and by either pressing + or -. (Change
the start temperature for when defros-
ting is to begin).
By using the right-hand arrow and
then pressing +, defrost can be started
manually. During defrost, hot refrigerant
circulates to the air heat exchanger.
VUBMI102
DEFROST
DEFROSTS
BETW. 2 DEFR
TIME LAST DEFR
FAN H OFF AT
DEFROST CURVE
MANUAL DEFR
Adjusted by:
Not adjustable
Not adjustable
Not adjustable
By the customer, if
necessary.
By the customer, if
necessary.
0S
0M
0M
12°C
0
DHP-AX – 29