AEG Protect D. 6000 (BP) Operating Instructions Manual page 55

Table of Contents

Advertisement

Description
Auto reboot
Auto bypass
start-up without
battery
Clear event log
lCD Contrast
Restore factory
settings
the "restore Factory settings" process is completed after the uPs is switched
off completely. Wait until the fans stopped to prevent the uPs internal eePrOM
overwriting.
Adjustable parameters
[enabled], [disabled]
"enabled " means the uPs outputs are
automatically reconnected after ensuing
switch-off, e.g. due to low battery voltage
after power is restored.
[enabled], [disabled]
"enabled" means uPs will have bypass
output when utility power on.
"Disabled" means uPs will not have bypass
output when power is on but could get
bypass output when uPs is in fault or overload.
[enabled], [disabled]
"active" means the uPs can be started
without installed battery system.
the number after "total events" shows how
many events are currently stored in the log.
Press the "enter" button for one second to
reset the event count to zero and clear the log.
[-5], [-4], ...[-1], [0], [+1], ...[+4], [+5]
the LcD contrast is adjustable and the valid
range is from -5 to +5.
[no], [yes]
setting only available in uPs stand-by mode.
• restoring the factory settings:
• returns all user-configurable settings to
default factory settings
• resets all pending on / off commands
• clears the alarm and event log
• after acknowledgement the uPs
conducts a new initialization process
55