AEG Protect D. 6000 (BP) Operating Instructions Manual page 12

Table of Contents

Advertisement

12
overload behavior
with existing network
overload behavior
Bypass
overload behavior
when on battery
short circuit protection
Battery
Autonomy time
Coupled
battery module
with integrated battery
1 add. battery module
2 add. battery modules
3 add. battery modules
4 add. battery modules
Battery check
(programmable):
Rated DC voltage
(DC link)
float voltage
Adjustment
temperature compensation
Battery charging current
(max.)
switch-off
to 102 % continuously;
≥ 102 % – <130 % for 2 min.
≥ 130 % – <150 % for 30 s
automatic seamless transfer to bypass mode (sBs)
to 130 % continuously;
≥ 130 % – <180 % for 1 min.
to 102 % continuously;
≥ 102 % – <130 % for 10 s
≥ 130 % for 100 ms
3 x i
for 100 ms
n
(cos ϕ = 0.9 lag / 100 % charged battery / 25°c)
D. 6000
D. 6000
(rated load)
(half load)
3 min.
9.5 min.
11 min.
27 min.
20 min.
46 min.
30 min.
68 min.
40 min.
91 min.
Daily, weekly, monthly
Protect D. 6000 180 Vdc
Protect D. 10000 240 Vdc
2.28 Vdc / cell (default 20°c)
charging voltage depending on temp.
2.21 Vdc / cell – 2.31 Vdc / cell in 0.01 V increments
20m V / 12 V-Block / °c
1.4 adc (Protect D. 6000)
1.7 adc (Protect D. 10000)
1.60 to 1.75 V / cell (load and temperature
dependent)
D. 10000
D. 10000
(rated load)
(half load)
4 min.
7.5 min.
9 min.
18 min.
15 min.
30 min.
21 min.
43 min.
27 min.
57 min.