AEG Protect D. 6000 (BP) Operating Instructions Manual page 13

Table of Contents

Advertisement

Battery voltage
type of battery
Recharging times
Communication
Interfaces
(DuAl Monitoring)
ePo contact
Relay load-carrying ability
shutdown software on CD
General information
Classification
full-load efficiency
(AC-AC / DC-AC)
full-load efficiency
(eCo / transfer time < 10ms)
Inherent noise (1m distance)
Cooling
operating temperature range 0°c bis +40°c
storage temperature range
Visual and audible alarm at 1.90 V / cell
sealed lead-acid battery (VrLa)
spec. type for high-current discharge
Protect D. 6000
Protect D. 6000 BP
Protect D. 10000
Protect D. 10000 BP
~ 3h to 90 % for internal battery
~9h / ~15h / ~21h / ~27h with 1 / 2 / 3 / 4 battery
extension(s)
rs232 (suB-D (9-pin)), usB
additional: communication slot for extensions
(e.g. relay card / snMP (PrO), etc.)
Potential-free
(optionally programmable as opener or closer)
250 Vac 3 a or 30 Vdc 3 a change-over contact
(programmable)
"compuWatch" for all popular operating systems,
inc. Windows, Linux, Mac, unix, novell, sun
VFi ss 111 acc. to iec 62040–3
Double-conversion technology
Protect D. 6000
Protect D. 10000
Protect D. 6000
Protect D. 10000
<55 dB(a)
external variable-speed cooling fan
recommended: +15°c to +25°c
(battery system dependent)
-15°c to + 60°c (uPs)
0°c to + 35°c (battery)
15 blocks at 12 V 5 ah
15 blocks at 12 V 9 ah
20 blocks at 12 V 9 ah
20 blocks at 12 V 9 ah
> 92 % / >89 %
> 93 % / > 90 %
> 96 %
> 97 %
13