Battery Specifications; High-Voltage Ups Battery Runtimes; Low-Voltage Ups Battery Runtimes; Environmental Specifications - HP R3000 User Manual

Hide thumbs Also See for R3000:
Table of Contents

Advertisement

Battery specifications

Feature
Type
Voltage
Charging

High-voltage UPS battery runtimes

Load, percent
20
50
80
100

Low-voltage UPS battery runtimes

Load, percent
20
50
80
100

Environmental specifications

Feature
Operating temperature
Nonoperating
temperature
Relative humidity
Operating altitude
Nonoperating altitude
Audible noise
Specification
12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at
25°C (77°F).
The battery modules have a battery string voltage of 120 V.
Complete charge takes no more than 48 hours. After
approximately 3 hours, the batteries reach 80% charge at
default nominal utility voltage and no load.
Estimated battery
runtime
40 minutes
12 minutes
6 minutes
4 minutes
Estimated battery
runtime
45 minutes
15.5 minutes
7 minutes
5 minutes
Specification
10°C to 40°C (50°F to 104°F); UL-tested at 25°C
(77°F)
-20°C to 50°C (-4°F to 122°F)
20% to 80%; noncondensing
Up to 2,000 m (6,600 ft) above sea level
15,000 m (49,212 ft) above sea level
Less than 45 dBA, normal operation
Less than 50 dBA, on battery power
Runtime with one ERM
125 minutes
50 minutes
30 minutes
24 minutes
Runtime with one ERM
142 minutes
55 minutes
34 minutes
26 minutes
Runtime with two ERMs
225 minutes
89 minutes
54 minutes
43 minutes
Runtime with two ERMs
256 minutes
99 minutes
60 minutes
47 minutes
Specifications 61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R/t3000Pavilion t3000 - desktop pc

Table of Contents