Specifications
UPS physical specifications
Parameter
Height
Depth
Width
Weight
Ambient operation
ERM physical specifications
Parameter
Height
Depth
Width
Weight
UPS input specifications
NOTE:
UPS model
R7000 NA/JPN
R7000 INTL
UPS output specifications
UPS model
R7000 NA/JPN
Value
17.1 cm (6.75 in)
73.4 cm (28.9 in)
43.7 cm (17.2 in)
75 kg (165 lb)
0~40°C
Value
12.7 cm (5 in)
71.9 cm (28.3 in)
43.8 cm (17.24 in)
63 kg (139 lb)
An asterisk (*) indicates the default setting.
Utility voltage
Available settings
frequency (Hz)
utility voltage (VAC)
50/60
200/208*/220/230/
240
50/60
200/208/220/230*/
240
Load
Circuit
segment
breaker
1
20 A¹
Dedicated
branch circuit
rating (A)
40
50 low input
32
Output receptacles Maximum current
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
Line cord
Nondetachable power
cord with NEMA
CS8265C plug
Nondetachable power
cord with 32 A IEC-309
plug
Specifications 50