A
IS THE PUMP
RUNNING?
YES
YES
IS THE FAN
RUNNING?
YES
YES
IS SPARK
GENERATION FOR
IGNITION
NORMAL?
YES
YES
IS THE BURNER
ALIGHT?
YES
YES
HAS THE
BOILER SAFETY
SHUTDOWN BEEN
ACTIVATED?
NO
NO
B
62
NO
NO
POWER TO
THE PUMP?
YES
YES
1 - Check that the pump
is not stuck
2 - Release/replace pump
NO
NO
POWER TO
FAN ?
YES
YES
1 - Replace fan
NO
NO
NO
NO
YES
YES
NO
NO
1 - Check DHW flowswitch
2 - Check pump cable
3 - Check/replace P.C.B.
1 - Check/replace
NO
NO
connection cable
2 - Check/replace P.C.B.
1 - Check/replace ignition
electrode
2 - Check ignition cable
3 - Check spark generator
4 - Check ignition electrode
cable
5 - Check/replace P.C.B.
1 - Check power supply of
gas valve
2 - Check/replace P.C.B.
3 - Check efficiency of
gas valve
4 - Replace gas valve
1 - Check if flame strikes
detection electrode
2 - Check soft-light gas
pressure
3 - Check/replace detection
electrode
4 - Check/replace P.C.B.
FC P013