11.3 Fitting the 5" Flue (Ø 80 / 125 Horizontal/vertical)
Should the flue require extending, the flue connections are
push fit, however, one flue bracket should be used to secure
each metre of flue.
N
: S
28
OTE
EE PAGE
FOR MAXIMUM AND MINIMUM FLUE RUNS
Once the boiler has been positioned on the wall, it is
necessary to insert the Ø80/125 adaptor (F
horizontal and vertical flue runs into the boiler flue socket
(not supplied with flue kit - Part No 3318095).
Push the adaptor onto the boilers flue connection, grease
the seals then add extensions or elbows as required, secure
the adaptor, using the clamp and screws provided.
To fit extensions or elbows it is first necessary to ensure that
the lip seal is fitted correctly into the inner flue, once
verified, it is simply necessary to push them together, no
clamps are necessary to secure the flue components.
Before proceeding to fit the flue, ensure that the maximum
flue length has not been exceeded (See the tables on Page
20) and that all elbows and bends have been taken into
consideration, the maximum flue length is 10 metres, for
each additional 90
o
elbow 1 metre must be subtracted from
the total flue length, and for each 45
subtracted from the total flue length (the height of the
vertical adaptor and a 45
and a 90
o
bend in Fig. 11.10).
N
: DO NOT
OTE
CUT THE VERTICAL FLUE KIT
26
. 11.8) for both
IG
o
0.5 metres must be
o
bend can be seen in Fig. 11.9
.
Fig. 11.9
.
Fig. 11.8
153
Fig. 11.10