Ariston GENUS PREMIUM EVO HP 45 Design, Installation And Servicing Instructions

Ariston GENUS PREMIUM EVO HP 45 Design, Installation And Servicing Instructions

Hide thumbs Also See for GENUS PREMIUM EVO HP 45:
Table of Contents

Advertisement

Quick Links

GENUS
PREMIUM EVO HP
WALL-HUNG CONDENSING
GAS BOILER
GENUS PREMIUM
EVO HP
45/65/85/100/115/150

Advertisement

Table of Contents
loading

Summary of Contents for Ariston GENUS PREMIUM EVO HP 45

  • Page 1 GENUS PREMIUM EVO HP WALL-HUNG CONDENSING GAS BOILER GENUS PREMIUM EVO HP 45/65/85/100/115/150...
  • Page 2: Table Of Contents

    INDEX Overview ........................3 Boiler protection devices ................29 Advice for the installer ..................3 Safety shut-off ...................... 29 CE labelling .......................3 Shutdown ....................... 29 Safety regulations ....................4 Table summarising error codes ..............29 Anti-freeze function ................... 30 Product description ....................5 Control Panel......................5 Thechnical area ....................
  • Page 3: Overview

    overview Advice for the installer CE labelling The installation and fi rst ignition of the boiler must be The CE mark guarantees that the appliance conforms to the performed by qualifi ed personnel in compliance with following directives: current national regulations regarding installation, and - 2009/142/CE relating to gas appliances in conformity with any requirements established by - 2004/108/CEE relating to electromagnetic compatibility...
  • Page 4: Safety Regulations

    overview Safety regulations Handle the appliance with suitable protection and with care. Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing. Key to symbols: During all work procedures, wear individual protective clothing and Failure to comply with this warning implies the risk of equipment.
  • Page 5: Product Description

    overview Control panel - Display Legend: Display 24/01/2011 12:25 Domestic Hot Water 44°C 40°C adjustment button +/- ON/OFF button Pressure gauge Flame detected Blue LED Esc button (Back) “encoder” programming knob Ok button programming key MODE button (Operation mode selection summer/winter) 10.
  • Page 6: Overall Wiew 45/65

    Overall wiew GENUS PREMIUM EVO HP 45/65 GENUS PREMIUM EVO HP 85/100...
  • Page 7: Overall Wiew 115/150

    product description GENUS PREMIUM EVO HP 115/150 Legend: Combustion analysis test point Flue thermostat Flame inspection glass Ignition electrode Ignitor Modulating fan Minimum water pressure switch Siphon Circulation pump with air release valve 10. Mixer 11. Silencer 12. Gas valve 13.
  • Page 8: Overall Dimension 45/65

    Overall Dimensions GENUS PREMIUM EVO HP 45/65 Ø 126 Ø 80,5 A. Central Heating Flow 1” M C. Gas Inlet ¾” M E. Central Heating Return 1” M A-C-E-F F. Condesate discharge GENUS PREMIUM EVO HP 85/100 A. Central Heating Flow 1” ¼ M C.
  • Page 9: Overall Dimension 115/150

    product description GENUS PREMIUM EVO HP 115/150 A. Central Heating Flow 1” 1/2 M A - C - E - F C. Gas Inlet 1” M E. Central Heating Return 1” 1/2 M...
  • Page 10: Technical Information 45/65/85/100

    product description Technical Data Model GENUS PREMIUM EVO HP CE Certifi cation (pin) 0063BT3414 Boiler type C13-C33-C43-C53-C83-B23-B23p-B33-B33p Max/min nominal calorifi c fl ow rate (Pci) Qn 41,0 / 12,2 58,0 / 17,4 80,0 / 20,0 88,3 / 22,1 Max/min nominal calorifi c fl ow rate (Pcs) Qn 45,6 / 13,6 64,4 / 19,3 88,9 / 22,2...
  • Page 11: Technical Information 115/150

    product description Model GENUS PREMIUM EVO HP CE Certifi cation (pin) 0063BT3414 Boiler type C13-C33-C43-C53-C83-B23-B23p- B33-B33p Max/min nominal calorifi c fl ow rate (Pci) Qn 109,0 / 27,3 140,0 / 35,0 Max/min nominal calorifi c fl ow rate (Pcs) Qn 121,1 / 30,3 155,6 / 38,9 Max/min power output (80°C-60°C) (Central Heating) Pn...
  • Page 12: Installation

    Genus Premium EVO HP is designed to work individually or in cascade (max 8 devices). GENUS PREMIUM EVO HP 45/65 Is necessary that all requirements are met by the rules and regulations for equipment equivalent to the total installed power generators.
  • Page 13: Gas Connection

    View of the Boiler Connections COUNTRY MODEL CATEGORIES GENUS PREMIUM EVO HP 45 GENUS PREMIUM EVO HP 65 GENUS PREMIUM EVOHP 45/65 GENUS PREMIUM EVO HP 85 GENUS PREMIUM EVO HP 100 GENUS PREMIUM EVO HP 115...
  • Page 14: Residual Head Of The Boiler

    installation The hydraulic system have to be dimensioned and complete with Graph representing the available circulation pump pressure all accessories that ensure the smooth operation. In particular it is necessary to provide all protective equipment and 1000 safety requirements by law. GENUS PREMIUM EVO HP 85/100 is not provided with pump.
  • Page 15: Appliances With Underfl Oor Heating

    installation Discharge of condensation High energy effi ciency produces some condensation which must be removed. To do so, use a plastic pipe placed so as to avoid the accumulation of any condensation inside the boiler. This pipe must be attached to a discharge siphon which can be checked when required.
  • Page 16: Water Circuit Diagram

    installation Water circuit diagram Legend: Manual air vent Main heat exchanger Detection Electrode C.H. Flow temperature probe C.H. Return temperature probe Minimum water pressure switch Siphon Circulation Pump (optional for 85/100/115/150) Gas valve 10. Modulating fan 11. Mixer 12. Ignition electrode 13.
  • Page 17: Connecting The Flue

    installation Connecting the Flue GENUS PREMIUM HP 45/65 The boiler is designed to operate in B mode (by drawing air from is equipped for connection the room) and in C mode (by drawing air from outside). to a 80/125 coaxial fl ue gas When installing an exhaust system be careful when handling the suction and exhaust system.
  • Page 18: Table Of Fl Ue Gas Exhaust Duct Lengths

    installation Table of fl ue gas exhaust duct lengths Type of air suction/fl ue gas exhaust ducting Maximum extension Combustion air drawn from the room Diameter exhaust-air (m) External fl ue gas exhaust Type of pipe Air drawn from the room (mm) ø...
  • Page 19: Electrical Connection

    L-N poles and the earth connection are all respected. Important! In the event that the power supply cable must be changed, replace it with specifi que cable supply by ARISTON. H05V2V2-F Important! Connection to the electricity mains supply must be...
  • Page 20: Electrical Diagram 45/65

    installation Electrical diagram For increased safety, ask a qualifi ed technician to perform a thorough check of the electrical system. The manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the malfunctioning of the electricity mains supply.
  • Page 21: Electrical Diagram 85/100

    installation GENUS PREMIUM EVO HP 85/100 Peripheral unit SOL TA1 FLAME HV connection Detection electrode FLAME LV connection Display Ignitor C.H. Return temp. probe CN14 Gas valve C.H. Flow temp. probe CN18 Fume thermostat CN25 Diverter valve Thermal fuse Modulating Circulation Minimum water pressure switch...
  • Page 22: Electrical Diagram 115/150

    installation GENUS PREMIUM EVO HP 115/150 Peripheral unit SOL TA1 FLAME HV connection FUSE 2A Detection electrode FLAME LV connection Display Ignitor C.H. Return temp. probe CN14 Gas valve C.H. Flow temp. probe Fume overheat CN18 thermostat CN25 Diverter valve Thermal fuse Minimum water pressure switch...
  • Page 23: Commissioning

    commissioning Start-up procedure Initial procedures Press the ON/OFF button on the control panel to switch on the boiler: To guarantee safety and the correct operation of the appliance, the display will light up. the boiler must be prepared for operation by a qualifi ed technician The initialisation procedure - indicated by the bar - begins.
  • Page 24: First Ignition

    commissioning First ignition Deaeration cycle 1. Make sure that: During the fi lling stage or if there is excess air in the system, The gas valve is closed; the deaeration cycle can be activated by holding the E The electrical connection has been properly carried out. button for 5 seconds.
  • Page 25: Cleaning Function And Combustion Analysis

    Once the calibration procedure is completed, analyse the CO2 values at minimum power. GENUS PREMIUM EVO HP 45/65/85/100 Checking the gas setting To carry out analyses of combustion, the cleaning function must be activated.
  • Page 26: Adjustment The Maximum Heating Power

    After these operations, it is advisable to check the gas fl ow on the 57,3 meter, following the instructions outlined in the technical data table. 39,8 GENUS PREMIUM EVO HP 45/65/85/100 34,4 26,9 21,7 19,7 17,3...
  • Page 27: Soft Light Adjustment

    commissioning Checking slow ignition power Gas changeover The boiler can be converted to use either methane (natural) gas The soft light can be adjusted between the maximum power and (G20) or L.P.G. ( G31) by an Authorised Service Centre. the minimum power. The display shows the value between “100”...
  • Page 28: Auto Function

    The various corresponding parameters should therefore be set (see Technical Area). To activate the function, press the AUTO button. For further information please refer to the ARISTON temperature adjustment manual. EXAMPLE 1: SINGLE ZONE SYSTEM (HIGH-TEMPERATURE) WITH ON/OFF ROOM...
  • Page 29: Boiler Protection Devices

    boiler protection devices The boiler is protected from malfunctions by means of internal Important If this shutdown occurs frequently, contact an authorised Technical Service checks performed by the electronic P.C.B., which stops the boiler Centre for assistance. For safety reasons, the boiler will permit a maximum of 5 from operating if necessary.
  • Page 30: Anti-Freeze Function

    boiler protection devices Anti-frost Device External P.C.B.’s The anti-frost function acts on the central heating fl ow temperature Zone 1 - Room sensor circuit open / short circuit probe, independently from other regulations, when the electrical Zone 2 - Room sensor circuit open / short circuit supply is turned on.
  • Page 31: Thechnical Area

    technical area TECHNICAL AREA - reserved for qualifi ed technician Example: Modifi cation of parameter 2.3.1 Max. Adjustable Central Heating Power Accessing the Technical Area allows for setting/confi guring the Proceed as follows: device according to the specifi c requirements of every installation 1.
  • Page 32 technical area Tecnical Area Service code ( reserved for qualifi ed technicians Turn the encoder and select code 234 and press OK Language, date and time - Follow the instructions of the display. Press OK button at each entry to save COMPLETE MENU - The parameters relating to each individual menu are listed in the following pages.
  • Page 33 2. 2. 0 Soft ignition from 0 to 100 2 = Modulating 2.2.0 Soft ignition GENUS PREMIUM EVO HP 45/65/85*/100* 60 % *= with Optional Pump Kit (Two speed) 2. 3. 9 Set Delta T Pump from 10 to 30 (°C)
  • Page 34 technical area description value description value notes notes 2. 5. 7 Anti-legionella Function 0 = OFF 2. 4. 4 Boost Time from 0 to 60 (minutes) 1 = ON Activated with the boiler connected to a tank by an NTC only enabled with Room Thermostat on/off and sensor temperature adjustment activated (parameter 421 or...
  • Page 35 technical area description value description value notes notes 4. 2. 1 Select Type of 0 = Fixed Flow 4. 2. 4 Room sensor Infl uence from 0 to 20 Thermoregulation Temperature to calculate the set- 1 = Basic point temperature To enabled Thermoreg.
  • Page 36 technical area description value description value notes notes 6. 2. 2 Zone 3 Slope from 1.0 to 3.5 5. 2. 3 Parallel curve shift Zone from - 14 to + 14 (°C) (high temperature) 2 Off set (high temperature) from 0.2 to 0.8 from - 7 to + 7 (°C) (low temperature) (low temperature)
  • Page 37 technical area description value notes 8. 2 BOILER 8. 2. 1 Fan Status 0 = OFF 1 = ON 8. 2. 2 Fan Speed - x100 RPM 8. 2. 3 Aperto 8. 2. 4 Diverter valve position 0 = D.H.W. 1 = Central Heating 8.
  • Page 38: Maintenance

    maintenance Instructions for opening the casing and performing an Instructions for opening the casing and performing an internal inspection (45/65) (85/100/115/150) internal inspection Before performing any work on the boiler, fi rst disconnect it from Before performing any work on the boiler, fi rst disconnect it from the electrical power supply using the external bipolar switch and the electrical power supply using the external bipolar switch and shut off the gas valve.
  • Page 39: General Comments

    maintenance Maintenance is an essential part of the safe and effi cient operation are used in conjunction with the anti-scaling and anti-corrosion of the boiler and ensures its durability. It should be performed function, in the quantities suggested by the manufacturer, at the according to the instructions given in current legislation.
  • Page 40: Data Plate Symbol

    maintenance Symbols used on the data plate mbar mbar Legend : 1. Brand 2. Manufacturer 3. Boiler model - Serial number 4. Commercial reference 5. certifi cation number 6. Destination country - gas category 7. Gas setting 8. Installation type 9.
  • Page 44 Ariston Thermo SpA Viale A. Merloni, 45 60044 Fabriano (AN) Asistencia Técnica www.aristonthermo.it 902 196 547 info.it@aristonthermo.com 420010271304...