Specific Device Wiring Instructions - Zeta NPAD Installation Manual

Analogue addressable fire alarm control panel
Table of Contents

Advertisement

PREMIER AD INSTALLATION MANUAL.

SPECIFIC DEVICE WIRING INSTRUCTIONS:

Fyreye Common Base
FE-CB
80-050
LOOP + IN
LOOP - IN
Fyreye Loop Isolator Base
FE-IB
80-090
-
LOOP - IN
LOOP + IN
Fyreye Addressable Sounder Base
FEA-SB
80-100
LOOP + IN
LOOP - IN
Approved Document No: GLT.MAN-105
Issue : 1.02
Authorised: GH
LOOP + OUT
LOOP - OUT
- -
+ +
IN
OUT
LOOP - OUT
LOOP + OUT
LOOP + OUT
LOOP - OUT
Date: 15/03/2004
Fyreye Addressable Detector Relay Base
FEA-RB
80-080
LOOP + IN
LOOP - IN
Note that on the Fyreye Loop Isolator Base, the
loop wiring connects to the terminal block on the
PCB and NOT to the Base Spring Screws.
The terminals are marked + & - in,
and +,- &- out.
The second –ve contact can be used
during commissioning to check the loop
integrity.
(Connect the –in to the spare – out.
Repeat for all isolators. Measure –ve line
resistance with a DVM. Return the –in
cable to its original terminal block.)
Zeta Glass Manual Call Point (Resetable)
ZT-MCP/AD (/R)
43-001 (43-002)
LOOP - IN
LOOP + IN
Software:31/3/04 & LC6
LOOP + OUT
C
RELAY
OUTPUT
LOOP - OUT
LOOP - OUT
LOOP + OUT
PAGE 8