8.1 LOOP CONTENTS FAULT FINDING

If the loop contents are different to what was expected, then there may be some wrong
connections to devices (they are polarity sensitive), or double addresses on the loop. (A
double address is when 2 or more devices have been set to the same address, so they
both answer at the same time.) If a panel detects a
double address, it will light the LEDs of the devices
with the problem. (NOTE: only detectors will light their
LED. Call points, sounders & interface modules will
not be indicated)
Return to the configuration menu & select option 5
(Dev status). Wait for the panel to read loop 1 address 001. (If loop 2 is needed, press
2,enter,001,enter).
The panel will give the device type & its analogue value. If the device is configured, there
will be an asterix (*) next to the device type. Number of devices should read 1 (a reading of
2 or more will mean a double address is present).
Press next to move to the next address on the loop. (The Previous button cannot be used
in this menu. It can only be used to scroll between multiple faults or alarms.) Read all
devices on the loop and compare with what was expected. If one address has 2 devices,
and another is "missing", the missing device could have a wrong address setting. If many
devices are missing, check that they have power. There may be more than one break in
the cable (the panel read all devices when it has a single break, and will report a loop fault
after a minute or so).

8.2 ADDRESS - ZONE TABLE

On the Premier AD, each available address corresponds to a zone, with 1-16 being in
zone 1, 17-32 being in zone 2, 33-48 in zone3 etc.
The table below shows the dip switch settings for each address, and the zone that address
will be in.
Eg to set address 37, find 37 in the table. It is at sw 7,6,5 = 010, and sw 4,3,2,1= 0101
Remembering that 0 = ON & 1 = OFF, the switch settings for 37 are:
7=ON, 6=OFF, 5=ON, 4=ON, 3=OFF, 2=ON, 1=OFF
SW 4,3,2,1
OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O 1111
SW
OOO
N/A
1
7,6,5 OO1
16
17
O1O
32
33
O11
48
49
1OO
64
65
1O1
80
81
11O
96
97
111
112
113
As an alternative to using this chart, use the table on the following page:-
Approved Document No: GLT.MAN-105
Issue : 1.02
Authorised: GH
2
3
4
5
18
19
20
21
34
35
36
37
50
51
52
53
66
67
68
69
82
83
84
85
98
99
100
101
114
115
116
117
Date: 15/03/2004
6
7
8
9
22
23
24
25
38
39
40
41
54
55
56
57
70
71
72
73
86
87
88
89
102
103
104
105
106
118
119
120
121
122
Software:31/3/04 & LC6
Device Type: HEAT *
Value:26
====================
Loop:1
Address:001
10
11
12
13
14
26
27
28
29
30
42
43
44
45
46
58
59
60
61
62
74
75
76
77
78
90
91
92
93
94
107
108
109
110
123
124
125
126
No Devs:1
LOOP 1
LOOP 2
15
ZONE 1
ZONE 9
31
ZONE 2
ZONE 10
47
ZONE 3
ZONE 11
63
ZONE 4
ZONE 12
79
ZONE 5
ZONE 13
95
ZONE 6
ZONE 14
111
ZONE 7
ZONE 15
N/A
ZONE 8
ZONE 16
PAGE 16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Premier ad

Table of Contents