First Fix Guidelines; Recommended Cable Types And Their Limitations; Mains Wiring Recommendations; Sounder Circuit Wiring Diagram - Zeta NPAD Installation Manual

Analogue addressable fire alarm control panel
Table of Contents

Advertisement

PREMIER AD INSTALLATION MANUAL.
If this equipment is not fitted and commissioned according to our guidelines, and the relevant
National Standards, by an approved and competent person or organisation, the warrantee may
become void.
4. FIRST FIX
All wiring must be installed to meet BS5839: Pt1: 2002 and BS 7671 (Wiring Regs) standards.
Other National standards of fire alarm system installation should be adhered to where
applicable.

4.1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS

Screened cables should be used throughout the installation to help shield the Panel from outside
interference and ensure EMC compatibility.
The two categories of cable according to BS5839: Pt1: 2002, Clause 26 "Fire Detection and Alarm
Systems for Buildings (Code of Practice for System Design, Installation and Servicing)" are:
Standard fire resisting cable – to PH30 classification of EN 50200
Enhanced fire resisting cable – to PH120 classification of EN 50200
(Note that all cables should be at least 1mm
On the Premier AD Panel the general recommendation would be to use standard fire resistant cable,
such as Firetuff™ , FP200 or an equivalent. These cables are screened, and will provide good ECM
shielding when properly grounded at the panel. Certain system specifications may demand the use
of a particular type of cable and due regard should be paid to this fact.
Depending on the environment, the cables may need mechanical protection (such as a conduit).

4.2 MAINS WIRING RECOMMENDATIONS

The Mains supply to the FACP is fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and
2.5mm²) or a suitable 3-conductor system, fed from an isolating double pole switch fused spur, fused
at 3A. IT SHOULD NOT BE CONNECTED THROUGH AN RCD. This should be secure from
unauthorised operation and be marked 'FIRE ALARM: DO NOT SWITCH OFF'. The supply must be
exclusive to the Fire Panel. MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE
GROMMETS PROVIDED
For information on how to connect Mains to the Panel's Power Supply PCB, see page 8.
Also refer to rating information on the mains cover inside the FACP
4.3 CONVENTIONAL SOUNDER CIRCUIT WIRING DIAGRAM
SND+
SND-
SOUNDER
- -
+
+
Note: If non-polarised alarm devices (eg some types of old mechanical bell, or a relay) are used, then
a diode will have to be placed in line with the device to enable fault monitoring. They may also need a
back EMF protection diode. (symptoms: Chattering sounder relays that don't turn off).
SND+
CONNECTOR
BLOCK
POLARISING
DIODE
SND-
BELL
- -
+
+
BACK EMF
DIODE
Approved Document No: GLT.MAN-105
Issue : 1.02
Authorised: GH
2
cross section
SOUNDER
SOUNDER
- -
- -
+
+
+
+
BELL
- -
- -
+
+
+
+
Date: 15/03/2004
SOUNDER
- -
+
+
BELL
RELAY
N C
C M
N O
Software:31/3/04 & LC6
10K
End of
Line Resistor
10K
End of
Line Resistor
PAGE 6