PREMIER SX INSTALLATION MANUAL.

11. PCB TERMINATION CONNECTIONS.

1 2 3 4 5 6 7 8 9
CONN 27

11.1 CONNECTIONS

Connection No
Description
1
ZONE 1 +&-
2
ZONE 2 +&-
3
ZONE 3 +&-
4
ZONE 4 +&-
5
ZONE 5 +&-
6
ZONE 6 +&-
7
ZONE 7 +&-
8
ZONE 8 +&-
9
SND 1 +&-
10
SND 2 +&-
11
CLASS CHANGE
12
FIRE RELAY NO/CM/NC
13
FAULT RELAY NO/CM/NC
14
BATTERY + & -
15
AC AC
16
EN54 supply - & +
17
CONN 1
18
CONN 27
19
CONN 26
20
CONN 5

11.2 FUSES

FUSE NO
DESCRIPTION
FS1
Charger Fuse
FS2
Battery Fuse
FS3
EN54 SUPPLY (NOT USED)
FS4
Sounder circuit 1
FS5
Sounder circuit 2
INLET FUSE
Mains Protection Fuse
Approved Document No: GLT.MAN-101
Issue : 1.95
Authorised: GH
FS4
FS5
SND1
SND2
400mA
400mA
FS1
CHARGER
1.6A
Use
Connect to Zone 1
Connect to Zone 2
Connect to Zone 3
Connect to Zone 4
Connect to Zone 5
Connect to Zone 6
Connect to Zone 7
Connect to Zone 8
Connect to sounder circuit 1 (sirens/bells)
Connect to sounder circuit 2 (sirens/bells)
Join terminals to activate sounders
Activates on fire (including test mode)
Normally powered ie NO is closed with no fault
Connect 2 x 12V SLA batteries in SERIES (ie 24V)
Connected to transformer secondary (30VAC)
NOT CONNECTED IN STAND ALONE PANEL.
20 way ribbon cable to display PCB
EARTH connection to display PCB & SCREEN TAG
Filtered mains to transformer
MAINS TERMINAL BLOCK
RATING
1.6A time delay 5 x 20mm glass
1.6A time delay 5 x 20mm glass
1.6A time delay 5 x 20mm glass
400mA time delay 5 x 20mm glass
400mA time delay 5 x 20mm glass
2A Quick Blow HBC 5 x 20mm ceramic
Date: 09/06/2004
FS3
FS2
En54 SUP
BATTERY
1.6A
1.6A
MAINS TO TRANSFORMER PRIMARY
CONN5
LIVE NEUT- EARTH
RAL
PAGE 15