Wiring Diagram
Note: Polarity must be observed on detector as indicated on schematic wiring diagram.
Earth terminal is provided to maintain earth screen continuity. It does not connect to this detector head.
Base Installation
Connect the zone wires to the appropriate terminal. Tighten with a correct sized screwdriver: a wrong screwdriver
may damage the screw heads.
Make sure that the base contacts are clean and unobstructed.
Note, the base model No. for MKII Series is MKII-CB or MKII-CB/D
Detector Head Installation
If there is still minor construction work in progress, the head may be fitted, provided that the dust cover is still in
place.
To fit the detector, mate the detector onto the base and rotate the detector in a clockwise direction until the
detector loads into the base. Continue to twist clockwise to secure it.
Model
There are 5 models of Fyreye II Conventional Detector.
Part No
Model No.
80-200
MKII-OP
80-202
MKII-HR
80-204
MKII-HF
80-206
MKII-OH
80-208
MKII-HF/CS90
Monitor state
In monitor state, the two red LEDs on the top cover will blink every 5 seconds.
See Fig-1.
Pre-alarm state
In pre-alarm state, LED pairs will blink a clockwise circle in every 5 seconds.
Fire alarm state
In fire alarm state, the two LEDs shown in Fig-1 will light. The other 3-pairs of LED will light for 0.5 seconds
rotating clockwise.
False alarms
In case of false alarm, the LED pairs will blink alternately. Check if the air around the detector is
clear. Fan the air around the smoke alarm if necessary, until the alarm turns off. If the false alarm
occurs frequently or continuously, arrange to have the unit serviced.
Sensitivity Read
Take the Sensitivity Test Wand making the receive diode against the light-emitting diode (see Fig-2).
And push the button of the Sensitivity Test Wand, the sensitivity will be displayed on LCD of Wand for a few
moments later.
Drift Compensation Limit
In the case of the smoke chamber reaching the end of it`s compensation limit, the detector will flash it`s LEDs
continuously to signal that the detector should be replaced. This can be confirmed with the Sensitivity Test Wand.
32-0067-r03
Zeta Alarms Limited, 72/78 Morfa Road, Swansea, SA1 2EN
Description
Conventional optical detector
Conventional A2R heat detector
Conventional A2S heat detector
Conventional optical and heat detector
Conventional CS heat detector
MKII-xx Installation Guide
CPR No.
0832-CPR-F0067
0832-CPR-F0071
0832-CPR-F0073
0832-CPR-F0069
0832‐CPR‐F1922
1 / 2
LPCB No
330n/01
330q/02
330q/01
330p/01
330q/06
Fig-1
Fig-2
17/10/2017

Advertisement

loading

Summary of Contents for Zeta MKII-HR

  • Page 1 In the case of the smoke chamber reaching the end of it`s compensation limit, the detector will flash it`s LEDs continuously to signal that the detector should be replaced. This can be confirmed with the Sensitivity Test Wand. 1 / 2 17/10/2017 32-0067-r03 Zeta Alarms Limited, 72/78 Morfa Road, Swansea, SA1 2EN...
  • Page 2 Alarm Current: 35-45mA at 24 volts Quiescent Current: 70uA Maximum Smoke Sensitivity: 0.08 dB/m - 0.12 dB/m Temperature class: A2R (for MKII-HR); A2S (for MKII-HF) , CS (for MKII-HF/CS90) Humidity Range: 0% to 95% Relative Humidity, non condensing Maintenance Information Fyreye Mk II detectors are generally installed as part of a fire alarm system.

This manual is also suitable for:

Mkii-hfMkii-opMkii-ohMkii-hf/cs9080-20080-204 ... Show all