6-4 Compaq 2000 Series UPS Operation and Reference Guide
Table 6-2
Troubleshooting Guide (After Start)
Symptom
Possible Cause
UPS
Utility power variations
frequently
switches
between
utility and
battery power
LED 11 is red
Protected devices are exceeding
(Load Level)
the UPS power rating
LED 9 is red
Low battery voltage
(Battery
Charge)
Insufficient
Battery service required
warning of
low batteries
Shutdown Delay configuration
inappropriate
LED 10 is red
Potential battery failure detected
(Battery
Service)
New batteries improperly
connected
continued
Suggested Action
The utility voltage is frequently
outside the UPS operating range.
Update the configuration.
Contact a qualified electrician to
make sure that utility power is
suitable for the UPS.
Remove one or more devices to
reduce the power requirements.
Make sure that devices are not
defective.
If the UPS is supplying battery
power, save current work and
shut down the system. Allow the
batteries to charge.
If the UPS is supplying utility
power, no user intervention is
required. Allow the batteries to
charge.
Allow batteries to charge for 24
hours, then initiate self-test. If
LED 10 is red, replace batteries.
Update the Shutdown Delay
from 5-seconds to 3-minutes.
Use Compaq Power
Management Software to specify
a suitable delay.
Allow batteries to charge for 24
hours, then initiate self-test. If
LED 10 is red, replace batteries.