Maintenance; Cleaning Or Replacing The Filter In The Domestic Ventilation Unit - Vaillant recoVAIR/3 SERIES Operating And Installation Manual

Recovair/3 series domestic ventilation unit with heat recovery and remote control
Table of Contents

Advertisement

6 Maintenance

6
Maintenance
Continued efficient operation, reliability and a long serv-
ice life as well as safety, require inspections and mainte-
nance work to be regularly carried out by an expert
technician on an annual basis.
You must employ a qualified technician to complete
such work.
Caution! You must always ensure that units mounted
high up and units mounted in roof spaces can easily be
reached using suitable equipment.
a
Caution!
We recommend making a maintenance agree-
ment. The operational reliability of the device
can be impaired, resulting in damage to proper-
ty or personal injury, if maintenance work is
not carried out.
The following must be checked:
– Soiling of the filters (cleaning or replacing the filters)
– Condensate discharge
– Function of the installed bypass unit
You as the owner or user may execute the following
maintenance work yourself:
– Clean and replace the filters in the domestic ventila-
tion unit.
– Clean and replace the filter in the bypass casing
(if installed).
– Clean the fresh air or exhaust air valves in the living
space.
– Reset the time interval for filter replacement in ac-
cordance with section 4.6 "Settings from the basic
display" Caution: Always ensure suitable access equip-
ment is used to gain access to eqipment installed at
high levels or in a loft space.
Caution!
a
Always ensure that the facilities installed high-
er or in the loft must be well accessible, if re-
quired, a suitable equipment must be used.
It depends on the contamination levels how often the fil-
ters must be cleaned or replaced. We recommend to
regularly check the filters during the initial operational
period and asses the need to clean them e.g. every
three months. If you then feel that the filters are only
slightly contaminated or dirty, you may extend the in-
terval.
h
Note
Replace the filters at least once a year or after
maximum 2000 operating hours.
You can clean the filters with a vacuum cleaner. If this is
not enough, the filters must be replaced. Cleaning the
filters with water or other liquids is expressly prohibited.
Dispose the used filters with the domestic waste.
12
6.1
Cleaning or Replacing the Filter in the
Domestic Ventilation Unit
To check and clean the filters, please proceed as fol-
lows:
e
Danger!
Risk of fatal electric shock from touching live
connections. Pull the mains plug before starting
to work on the device.
• Open the left front flap.
• Pull the filter out of the unit.
• Remove the filter handles from the filters.
• Observe the descriptions in the inner side of the door.
Fig. 6.1 Filter replacement
• The filters are to be cleaned or replaced depending on
the degree of soiling.
Caution!
a
Before inserting the filters, please ensure the
correct positioning in order to avoid damaging
of the filters.
• Position the filter handles on the clean or new filters.
On the one side, the filter handles are fitted with guides
which must be pushed into the grooves in the unit.
– The upper filter is mounted with these guide pointing
to the bottom.
– The lower filter is mounted with the guide pointing to
the top.
• Push the filters back into the unit.
• Close the front flap.
• Plug in the mains plug into the plug socket.
The unit is now ready for operation.