Installing the Avaya G350 Media Gateway
Step 3: Attach ground conductors

Connect the safety ground

Proper grounding of the G350 Media Gateway installation safeguards the system, users and service
personnel by providing protection from lightning, power surges, AC mains faults, power crosses on
central office trunks, and electrostatic discharge (ESD).
Local electrical installation codes must be followed when installing the G350.
!
DANGER:
Connection of both grounds (through the AC Power Cord and the Supplementary
Ground Conductor) is required for safe operation of the G350 Media Gateway.
!
An improper ground can cause electrical shock as well as equipment failures and service outages.
To attach the ground wires:
1
Remove the ground screw on the rear of the chassis adjacent to the ground symbol.
2
Place the ring terminal of the 10 AWG (4.0 mm
3
Replace the ground screw to the chassis and securely tighten the screw such that it cannot be
loosened without the use of a tool.
If the ground block has been purchased: The ground block is provided for use with more than
one G350 in the rack. It is usually mounted by the customer electrician.
4
Cut the Supplementary Ground Conductor (which has one end attached to the grounding screw on
the chassis) to the length needed to terminate it into one of the terminals of the ground block. Do
not coil the Supplementary Ground Conductor.
5
Attach one end of the remaining 10 AWG (4 mm
ground block and the other end to an approved ground.
6
Cut this ground wire to the length needed to reach the approved ground. Do not coil this wire.
If the ground block is not being used, simply:
1
Attach the Supplementary Ground Conductor to an approved ground.
2
Connect the AC power cable to the inlet receptacle on the rear of the chassis.
You have now mounted the fully equipped G350 Media Gateway and connected to electrical ground
conductors. You are now ready to connect power.
30
WARNING:
) Supplementary Ground Conductor on the screw.
2
2
) ground wire to one of the terminals in the
Installation of the G350 Media Gateway