BMTW-SVU02C-EN
The override control status for each property is displayed within
square brackets. Each property can be controlled to the following con-
trol status:
Blank—no override status is shown for the present value property
when communications are down. Some properties do not support
displaying the control status (for example, properties with more
than two states: auto/manual).
Auto—the property is being controlled by the building automation
system.
Manual—the property is controlled based on an override request
by the operator.
Manual Request—An override has been requested by the opera-
tor, but the property is currently being controlled by an applica-
tion or operator with a higher priority level as shown in the
priority list (see Figure 18 on page 22).
5. From the list of displayed properties, press the button for the prop-
erty you want to override. Figure 17 shows an example of the override
screen for the Present Value property.
Figure 17: Present Value Property Override Screen
6. Select a new value from the override screen.
7. A confirmation screen displays. Press Yes to confirm your changes
and return to the Manual Control screen. The new value appears on
the selection button associated with the overridden property.
Note:
If the present value or lighting value property cannot be over-
ridden at this time, you will need to add the request to the over-
ride control list, see "Making a Manual Request" on page 22.
Changing System Values