Alarm And Power Leds; Watchdog Status; Modem Interface; I/O Bus Switch S2 - Honeywell XL 800 Series Installation And Commissioning Instructions

Hide thumbs Also See for XL 800 Series:
Table of Contents

Advertisement

Mounting/Dismounting Modules

Alarm and Power LEDs

The XCL8010AU Controller Module is equipped with an alarm
LED and a power LED.
Fig. 32. Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Table 17. Controller alarm LED
Off
Normal operation
On
Watchdog alarm output is powered
• The controller has encountered a hardware
problem
• The application has a fault
• The controller has been powered up without
an application or the operator has manually
stopped the application.
In this case, the LED will light up 13 minutes
after power-up without application
Flashing
The watchdog alarm output has not yet been
powered, although the controller has
encountered a problem.
The controller performs a warm start.
If problem persists, the LED will become lit
constantly, see above.
See section "Troubleshooting" on page 31.
Power LED (2, green)
Table 18. Controller power LED
On
Normal operation
Flashing
One or more of the internal voltage supplies
are outside of the permissible ranges.
The controller stops operation.
Check wiring or see section
"Troubleshooting" on page 31.
Goes out
• The operator has activated the reset
briefly
button
• The controller is performing a warm start
EN1B-0410GE51 R0908A

Watchdog Status

Table 19. Watchdog status (terminal 4)
status
Failure (= alarm)
Normal operation

Modem Interface

NO CONNECTION.

I/O Bus Switch S2

The XCL8010AU Controller Module features a 2-position I/O
Bus switch S2.
I/O Bus switch S2 must be set in accordance with the kind of
I/O modules connected to communication terminals 71, 72
and 75, 76 of the XCL8010AU Controller Module.
Terminals 71, 72 and 75, 76 must be all connected either to
Panel Bus I/O modules or to L
The default setting is Panel.
Fig. 33. I/O Bus switch S2
Table 20. I/O Bus switch settings
communication
L
W
Bus only
ON
ORKS
Panel Bus and L
W
ON
ORKS
L
W
B
modules connected to
ON
ORKS
US
terminals 11 ─ 14 of the XCL8010AU
Controller Module
Panel Bus connected to terminals 71, 72 or
75, 76 of the XCL8010AU Controller
Module
20
Excel 800
signal on terminal 4
24 V
0 V
W
Bus I/O modules.
ON
ORKS
S2 setting
LON
Bus
Panel
Panel

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents