Alarm LED (red)

case
alarm LED
1
OFF
2
ON
3
Flashing
Service LED
L
W
ON
ORKS
The L
W
service LED of the XCL8010AU Controller Module displays the following flashing patterns indicating possible
ON
ORKS
failure modes:
EN1B-0410GE51 R0908A
Table 38. XCL8010AU alarm LED
meaning
Normal operation
Watchdog alarm output is powered
– The controller has encountered a
hardware problem
- or -
– The application has a fault
- or -
– The controller has been powered up
without an application or the operator
has manually stopped the application,
e.g., using XL-Online.
In this case, the LED will light up
13 minutes after power-up without
application
Although the controller has encountered a
problem, the watchdog alarm output has not
yet been powered.
If problem persists, the LED will become lit
constantly, see case #2.
The controller performs a warm start.
Fig. 50. Flashing pattern of the L
No action necessary
Try powering down and then
powering up the XCL8010AU.
If problem persists, check and – if
necessary – reload the application.
If problem still persists, replace
hardware
If it happens only once, the controller
has performed a restart
If, however, it happens multiple times,
then there is an application or hardware
problem (see case #2)