Permissible Loads; Status Leds With Manual Overrides - Honeywell XL 800 Series Installation And Commissioning Instructions

Hide thumbs Also See for XL 800 Series:
Table of Contents

Advertisement

Excel 800
Table 34. Description of Relay Output Module terminals
terminal
signal
2-wire communication bus
71, 75
COM a
(LON/Panel Bus)
2-wire communication bus
72, 76
COM b
(LON/Panel Bus)
73, 77
Power supply
24 V~
74, 78
24 V~0
Power supply
11
Relay 1 N.O. contact
REL1 N.O.
12
Relay 1 N.C. contact
REL1 N.C.
13
relay 1 common contact
R1 COM
For connection of relay 1 common via
14
R1 COM
cross connector*
21
Relay 2 N.O. contact
REL2 N.O.
22
Relay 2 N.C. contact
REL2 N.C.
23
Relay 2 common contact
R2 COM
For connection of relay 2 common via
24
R2 COM
cross connector*
31
Relay 3 N.O. contact
REL3 N.O.
32
Relay 3 N.C. contact
REL3 N.C.
33
Relay 3 common contact
R3 COM
For connection of relay 3 common via
34
R3 COM
cross connector*
41
Relay 4 N.O. contact
REL4 N.O.
42
Relay 4 N.C. contact
REL4 N.C.
43
Relay 4 common contact
R4 COM
For connection of relay 4 common via
44
R4 COM
cross connector*
51
Relay 5 N.O. contact
REL5 N.O.
52
Relay 5 N.C. contact
REL5 N.C.
53
Relay 5 common contact
R5 COM
For connection of relay 5 common via
54
R5 COM
cross connector*
61
Relay 6 N.O. contact
REL6 N.O.
62
Relay 6 N.C. contact
REL6 N.C.
63
Relay 6 common contact
R6 COM
For connection of relay 6 common via
64
R6 COM
cross connector*
Shield connection (functional earth),
25
internally connected to the DIN rail
* Do not connect by wire!
comment
29

Permissible Loads

Table 35. Permissible loads of Relay Output Modules
per relay output
24 VAC, 60 Hz
module (total)
12 A
(common)
24 VDC
12 A resistive, 12 A, 0.6 PF
per normally open
24 VAC, 60 Hz
contact (common)
4 A
24 VDC
4 A resistive, 4 A, 0.6 PF
per normally
24 VAC, 2 A, 60 Hz
closed contact
24 VDC
(common)
4 A resistive, 4 A, 0.6 PF

Status LEDs with Manual Overrides

1
2
3
Fig. 46. Manual overrides (toggle switches)
The XFR824AU and XFLR824AU Relay Output Modules are
equipped with six manual overrides: one for each relay
output. These toggle switches can manually be set to either
"auto" or "0" or "1".
Table 36. Relay Output Module status LED behavior
mode
automatic mode, state
"logical ON"
automatic mode, state
"logical OFF"
override mode (setting "0")
override mode (setting "1")
*As configured during engineering.
Description of the I/O Modules
max. load
4
5
6
Honeywell
--1
--0
--AUTO
!
N.O.*
N.C.*
LED
(direct)
(reverse)
ON
ON
OFF
OFF
OFF
ON
flashes
OFF
ON
flashes
ON
OFF
EN1B-0410GE51 R0908A