NAPCO Gemini GEM-P3200 Installation Instructions Manual page 49

Control panel/communicator
Hide thumbs Also See for Gemini GEM-P3200:
Table of Contents

Advertisement

WI817F 10/05
Telemetry Trouble
If any device connected to the on-board Serial Port (such as a Home Automation system or AES Radio) fails to respond to a poll
by the control panel, a Telemetry Trouble system trouble will result. On the PCD-Windows System Features screen, enable Teleme-
try Trouble: = XT to report on alarm or activate and output. On the PCD-Windows System Reporting Codes screen, program a re-
porting code for Telemetry Trouble.
Keypad readout will be:
The event Log will read:
Keypad programming
Telemetry Trouble:
Telemetry Failure
If the device connected to the on-board Serial Port (such as a Home Automation system or AES Radio) is not able to carry out its
intended function, it can send a signal to the control panel, and a Telemetry Trouble system trouble will result. On the PCD-Windows
System Features screen, enable Telemetry Failure: = XF to report on alarm or activate and output. On the PCD-Windows System
Reporting Codes screen, program a reporting code for Telemetry Failure.
Keypad readout will be:
The event Log will read:
Trouble Restore:
Keypad programming
Telemetry Failure
Telephone Numbers
Dialing Prefix
To report to a central station, Telephone Number 1 must be programmed. Telephone Number 2 is programmed for Backup Re-
porting; Telephone Number 3 is programmed for Double or Split Reporting.
Private telephone systems may require a Dial-Tone Detection "E" or Pre-Dial Delay "D", followed by an access number to obtain
an outside line. (See Access Number for Outside Line.)
It should be noted here that the telephone number need not actually start in the first location shown, and may not end in the last.
Extra locations have been provided to allow for one or more prefix digits: a Pre-Dial Delay "D" or a Dial-Tone Detection "E". What is
important is that the telephone number, with its associated Pre-Dial Delay, Access Number, and Dial-Tone Detection, be wholly con-
tained within that group of locations, and that they be in their proper sequence.
If needed, a Dialing Prefix of up to 20 digits may be programmed. This prefix will be dialed immediately before the programmed
Central Station telephone numbers.
Test Timer
Cancel Next Test Timer Report on Any Report
The test timer schedule is programmed using NAPCO's PCD-Windows Quickloader Software. If Test Timer is programmed, an
automatic test report will be transmitted to the central station on the scheduled day(s) at the scheduled time. (UL installations require
a report at least every 24 hours). To report test timer, select Report Test Timer and program a report code. Program the Test Timer
event schedule and reporting time.
If Cancel Next Test Timer Report on Any Report is programmed, any report will cause the next test-timer transmission to be
aborted, however subsequent test-timer transmissions will report as scheduled. Do not program this feature in UL installations.
Timeout
Specifies the length of time that an alarm, alert, or delay will remain active. Auxiliary Output Access Control Time, Abort-Delay
Time, and Chime Time must be programmed, or the feature will not activate. See Time Selection.
L
NAPCO Security Systems
E58-00 SERVICE
TELEMETRY TRBL
TROUBLE: TELEMETRY
TROUBLE RESTORE: TELEMETRY
Address Location 1099 = [ ][ ]
E59-00 SERVICE
TELEMETRY COMM
TROUBLE: TELEMETRY FAIL
TELEMETRY FAIL
Address Location 1100 = [ ][ ]
4 - Telemetry Trouble
8 - Telemetry Fail
4 - Telemetry Trouble
8 - Telemetry Fail
X
GEM-P3200 Installation Instructions