WI817F 10/05
When a fire zone is bypassed the panel will go into a fire trouble condition. It will also transmit the fire trouble to the CS, if
programmed to do so.
Zones 1-9 are entered as 01 - 09.
Loop Response (750mS required for UL installations)
Loop response is the amount of time in milliseconds (mS) that a normally-closed circuit must remain open, or a normally-open
circuit must remain closed, to trigger an alarm. The slower the loop response, the more immune the system will be to intermittents
("swingers"). Loop response times for Zones 1 through 8 are programmed into the control panel; those for Zones 9 through 32 loop
responses are selected at the respective keypad configuration mode or expansion module jumper. (Refer to keypad instructions and
EZM Installation Instructions.)
Selectable loop-response times for Zones 1–8 are:
750mS (.75 sec.): The slowest loop-response time, recommended for use with magnetic contacts, window foil, etc. Unless pro-
grammed otherwise, loop-response time will be 750mS for all zones.
50mS (.05 sec.): Used for momentary Panic Buttons and area-protection devices, such as photoelectric eyes, passive infrared
sensors, floor mats, etc.
20mS (.02 sec.): An extremely fast loop response used primarily for window bugs.
Low Battery (Required for UL Mercantile installations)
A low-battery system trouble will annunciate at the keypad when the battery terminal voltage drops below normal. This condition
may signal a local sounding device, report to a central station (program Panel Low Bat Report Code), or both. If a battery is installed
and low terminal voltage is detected, a restore will not occur until the battery is recharged to its specified level and passes a dynamic
test. The dynamic test may be initiated manually by pressing the
by the panel.
In wireless installations, when displaying RF transmitter status, a "LoBatt" indication denotes a low-battery condition at the trans-
mitter.
Master Security Code
Dealer Security Code
Download Security Code
The factory-programmed Master Security Code (printed on the label affixed to the micro can) is unique and cannot be changed.
Use this code to enter the Dealer Program Mode to program (or change) the Dealer Security Code. If a Dealer Security Code is pro-
grammed, both the Dealer Security Code and the Master Security Code will work. However, should system RAM fail, only the Master
Security Code will work.
The Dealer Security Code is needed to enter the Dealer Program Mode, thus allowing the dealer to program codes, zone fea-
tures, reporting features and zone descriptions (see Programming Manual WI818 and/or WI1148). This code may be changed as
required.
Important! The label containing the Master Security Code should be removed. Record the code in a secure place for reference
as programming changes cannot be made without it (or the Dealer Security Code).
To change the Dealer Security Code, access the Direct Address Program Mode. Advance to the "PROG" screen, then change
the 6-digit code as required.
The Download Security Code is the six-digit code required to establish connection to the PCD-Windows Software.
Memory Failure
A User or Dealer Memory error will cause the sounder to pulse, the "SYS/TRBL" reminder to flash, and the display to read "E19-00
USER MEM ERROR " or "E20-00 DEALER MEM ERROR". Press the
the "SYS/TRBL" reminder). Activate RESET SYSTEM TROUBLE to manually reset the system trouble. A Memory Failure can be pro-
grammed to activate an alarm output and/or report using its associated system Report Code.
Modem II CS Format
Modem IIe CS Format
The GEM-P3200 control supports Radionics Modem II as well as Modem IIe central station reporting format.
Never Arm (Do not use for primary Burglary protection)
A zone programmed as Never Arm cannot go into alarm. If tripped, it will display at the keypad when the DISPLAY STATUS
function is selected. A chime will sound at the keypad while armed or disarmed, if Chime is also programmed for that zone and en-
abled. This feature is suggested for use as a garage-door or driveway monitor, or similar application.
No EOL Resistor
Program for any zone not wired with a 2200 Ohm end-of-line resistor (Napco Part No. EOL2.2K). This will disable any zone-
short indication (if programmed, Day Zone Short is disabled). If not programmed, an end-of-line resistor must be installed. Note:
This selection is automatically disabled for zones selected as Fire. Do not program for UL installations.
One-Button Arming See Easy Arming
Opening Report
Opening Report Only After Alarm Report (Do not program for UL installations)
Opening and closing reports are generally used in commercial installations. On disarming, the communicator can send an Open-
ing Code for Users 1–48 (Opening Report), or it may transmit only when the control panel is disarmed after an alarm has been re-
ported (Opening Report Only After Alarm Report). (Note: Key Fobs 1–8 report as Users 25–32). Subscriber Identification Numbers
L
NAPCO Security Systems
C
button, or it will be initiated automatically, every four hours,
C
button to silence the sounder ("SYSTEM READY" will display, along with
X
GEM-P3200 Installation Instructions
Page 43