NAPCO Gemini GEM-P3200 Installation Instructions Manual page 45

Control panel/communicator
Hide thumbs Also See for Gemini GEM-P3200:
Table of Contents

Advertisement

WI817F 10/05
Receiver Format
The communicator can be programmed to transmit to any standard central-station receiver. A receiver format must be entered
for each telephone number used, but a different format may be assigned to each.
Refer to Backup Report on Telco 2 and Report Telco 3 to determine whether or not Telephones 2 and/or 3 will be programmed.
Call the central station for each telephone number used to confirm the type of receiver in use. Select the receiver format entry for
each telephone number from the following table.
ENTRY
RECEIVER FORMAT
(blank)
Ademco, Silent Knight Slow
1
Sescoa, Vertex, DCI, Franklin
2
3
4
Radionics, DCI, Franklin
5
Universal Hi-Speed
8
9
A
Radionics Modem 2*
B
C
D
0
*These formats do not use programmable codes, but Event ID Codes to identify the type of zone as follows:
1 – Fire
2 – Panic
3 – Burglary
4 – Holdup
7 – Gas Alarm
8 – Heat Alarm
A – Auxiliary Alarm (keypad displays "0")
B – 24-Hour Auxiliary Alarm
Relay Control (External Relays)
In addition to the three relays provided on the motherboard, up to 24 external relays (8 per RB3008 Relay Module) or X-10 de-
vices (24 per GEM-X10 module) may be controlled from the keypad, by event or by schedule through the use of PCD-Windows
downloading software. Program these outputs to activate by event on PCD-Windows External Relay Control screen, or by schedule
on the Event Scheduler screen.
Relay Follows Zone
External Relays can be programmed to follow an open or shorted zone. On the PCD-Windows External Relay Control screen,
program the External Relay to "follow " an open zone, or to "follow" a shorted zone.
Relay Outputs See Alarm Outputs
Relay / X-10 Mapping
It is possible to have a relay or X-10 device activate for multiple events, with a maximum of 24 events. This allows the relay or X-
10 device to be activated by multiple events or conditions. This is programmed by assigning or mapping events to relay numbers.
PCD Windows must be used to program Relay/X-10 mapping. Referring to the PCD-Windows External Relay Control screen, the
"Relay / Entry#" column typically indicates the number of the relay which will accept the commands on that line. However, the "Map"
column, which is used to transfer the function defined on that line to a device on another line.
Remote Panic See Panic Zone
Report Digital Dialer Exit Error/Recent Closing
A Recent Closing transmission is sent if an alarm occurs within two (2) minutes after the expiration of the Exit Time. If the user num-
ber is available, it is included in the Recent Closing transmission. Note: Recent Closing transmissions are not sent for fire alarms.
Report Telco 1
Report Telco 3 (Double or Split Reporting)
Alarms, alarm restores, troubles and trouble restores may be selected individually for each zone. Violation of a zone selected to
report will communicate the code(s) selected for that zone to the central station.
Normally, Report Telco 1 is used to report to the central station. Report Telco 3 is used when certain zones will report to a differ-
ent receiver (split reporting); Report Telco 1 and Report Telco 3 are both used on the same zone to report to two receivers succes-
sively (Double Reporting). (Double Reporting requires a successful report to Telco 1 before reporting to Telco 3). Also see Backup
Report on Telco 2.
Reset Day Zone with Arm/Disarm Only See Day Zone
L
NAPCO Security Systems
DATA FREQ. (Hz)
1900
1800
1850
Radionics Fast
1900
Silent Knight Fast
1800
1850
Radionics BFSK
FBI 4/3/1*
SIA*
Ademco Point ID*
Ademco Express (Touch-tone 4/2 Format)
Radionics Modem IIe
(SIA CP-01 Requirement: 4.2.2.6)
DUTY CYCLE
INTERDIGIT TIME
(ON/OFF)
60/40mS
600mS
30/20
800
13/12
400
40/30
560
60/40
600
30/20
350
Modem Formats
X
GEM-P3200 Installation Instructions
Page 45