Setting The Restart Delays; Setting The Restart Delays; Reading Out Of The Restart Delays - ADDER ePowerSwitch 8XS User Manual

Epowerswitch 8xs is a power distribution and control unit that enables power management of 8 devices through an rs-232 or rs-485 connection
Hide thumbs Also See for ePowerSwitch 8XS:
Table of Contents

Advertisement

ePowerSwitch 8XS

6.3.5. Setting the restart delays

This command enables to set the Restart Delay individually for each Power Outlet. The Delay value can
be between 1 and 255 seconds (4 min 15 sec).
Command to be sent to the ePowerSwitch 8XS:
TRxy=z[CR]
Reply from the ePowerSwitch 8XS:
TRxy=z[CR]
Explanations:
Parameter
x
address of the ePowerSwitch
y
number of the Power Outlet
z
timer value
Examples:
TR31=17 Set Restart Delay of the Power Outlet #1 of ePowerSwitch #3 to 17 sec
The ePowerSwitch 8XS accepts lower case and upper case commands.
The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by
the character [CR].

6.3.6. Reading out of the restart delays

This command enables to read out the restart delay individually for each power outlet.
Command to be sent to the ePowerSwitch 8XS:
TRxy[CR]
Reply from the ePowerSwitch 8XS:
TRxy=z[CR]
Explanations:
Parameter
x
address of the ePowerSwitch
y
number of the Power Outlet
z
timer value
The ePowerSwitch 8XS accepts lower case and upper case commands.
The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by
the character [CR].
Page | 15
Value
1 to 16
specifies the address of the ePowerSwitch 8XS
1 to 8
specifies the number of the Power Outlet
1 to 255
set the Restart Delay (in sec)
Value
1 to 16
specifies the address of the ePowerSwitch 8XS
1 to 8
specifies the number of the Power Outlet
1 to 255
shows the Restart Delay (in sec)
Function/Remark
Function/Remark

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents