6.3.3. Setting of the power up delays

This command enables to set the Power Up Delay individually for each power outlet. The Delay value can
be between 1 and 255 seconds (4 min 15 sec).
Command to be sent to the ePowerSwitch 8XS:
TUxy=z[CR]
Reply from the ePowerSwitch 8XS:
TUxy=z[CR]
Explanations:
Parameter
x
address of the ePowerSwitch
y
number of the power outlet
z
timer value
Examples:
TU12=2
Set power up delay of the power outlet #2 of ePowerSwitch #1 to 2 sec
T163=10 Set power up delay of the power outlet #3 of ePowerSwitch #16 to 10 sec
The ePowerSwitch 8XS accepts lower case and upper case commands.
The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by
the character [CR].

6.3.4. Reading out of the power up delay(s)

This command enables to read out the power up delay individually for each power outlet.
Command to be sent to the ePowerSwitch 8XS:
TUxy[CR]
Reply from the ePowerSwitch 8XS:
TUxy=z[CR]
Explanations:
Parameter
x
address of the ePowerSwitch
y
number of the Power Outlet
z
timer value
The ePowerSwitch 8XS accepts lower case and upper case commands.
The ePowerSwitch 8XS sends its reply only after having received a valid command terminated by
the character [CR].
Value
1 to 16
specifies the number of the ePowerSwitch 8XS
1 to 8
specifies the number of the power outlet
1 to 255
set the power up delay (in sec)
Value
1 to 16
specifies the number of the ePowerSwitch 8XS
1 to 8
specifies the number of the power outlet
1 to 255
shows the power up delay (in sec)