Chapter 4 List of Data Settings

4.4 Extended Function Mode

Code
Function name
A001 Frequency source setting
A002 Run command source setting
A003 Base frequency setting
A203 Base frequency setting, 2nd motor
A303 Base frequency setting, 3rd motor
A004 Maximum frequency setting
A204 Maximum frequency setting, 2nd motor
A304 Maximum frequency setting, 3rd motor
A005 [AT] selection
A006 [O2] selection
A011 [O]-[L] input active range start frequency 0.00 to 99.99, 100.0 to 400.0 (Hz)
A012 [O]-[L] input active range end frequency
A013 [O]-[L] input active range start voltage
A014 [O]-[L] input active range end voltage
[O]-[L] input active range start frequency
A015
selection
A016 External frequency filter time const.
A017 Easy sequence function selection
A019 Multispeed operation selection
A020 Multispeed frequency setting
A220 Multispeed frequency setting, 2nd motor 0.0 or "start frequency" to "maximum frequency, 2nd motor" (Hz)
A320 Multispeed frequency setting, 3rd motor
A021 Multispeed 1 setting
A022 Multispeed 2 setting
A023 Multispeed 3 setting
A024 Multispeed 4 setting
A025 Multispeed 5 setting
A026 Multispeed 6 setting
A027 Multispeed 7 setting
A028 Multispeed 8 setting
A029 Multispeed 9 setting
A030 Multispeed 10 setting
A031 Multispeed 11 setting
A032 Multispeed 12 setting
A033 Multispeed 13 setting
A034 Multispeed 14 setting
A035 Multispeed 15 setting
A038 Jog frequency setting
A039 Jog stop mode
*1 This setting is valid only when the OPE-SR is connected.
Monitored data or setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block),
02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2),
06 (pulse-string input), 07 (easy sequence),
10 (operation function result)
01 (control circuit terminal block), 02 (digital operator), 03 (RS485),
04 (option 1), 05 (option 2)
30. to "maximum frequency " (Hz)
30. to "maximum frequency, 2nd motor" (Hz)
30. to "maximum frequency, 3rd motor" (Hz)
30. to 400. (Hz)
30. to 400. (Hz)
30. to 400. (Hz)
00 (switching between O and OI terminals),
01 (switching between O and O2 terminals),
02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1),
04 (switching between O2 and keypad potentiometer) (*1)
00 (single),
01 (auxiliary frequency input via O and OI terminals) nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible),
03 (disabling O2 terminal)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0. to "[O]-[L] input active range end voltage" (%)
"[O]-[L] input active range start voltage" to 100. (%)
00 (external start frequency), 01 (0 Hz)
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
00 (disabling), 01 (enabling)
00 (binary: 16 speeds selectable with 4 terminals),
01 (bit: 8 speeds selectable with 7 terminals)
0.0 or "start frequency" to "maximum frequency" (Hz)
0.0 or "start frequency" to "maximum frequency, 3rd motor" (Hz)
0.0 or "start frequency" to "1st maximum frequency" (Hz)
0.0 or "start frequency" to "2nd maximum frequency" (Hz)
0.0 or "start frequency" to "3rd maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
0.0 or "start frequency" to "n-th maximum frequency" (Hz)
"Start frequency" to 9.99 (Hz)
00 (free-running after jogging stops [disabled during operation]),
01 (deceleration and stop after jogging stops [disabled during
operation]),
02 (DC braking after jogging stops [disabled during operation]),
03 (free-running after jogging stops [enabled during operation]),
04 (deceleration and stop after jogging stops [enabled during
operation]),
05 (DC braking after jogging stops [enabled during operation])
4 - 4
Setting
Change
Default
during
during
operation
operation
(allowed
(allowed
_FF
or not)
or not)
02
02
60.
60.
60.
60.
60.
60.
00
03
0.00
0.00
0.
100.
01
31.
00
00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.00
00

Hide quick links: