Over Temperature Blink Pattern - Qlogic SANbox 5600 Series Installation Manual

Sanbox 5600 series fibre channel switch
Hide thumbs Also See for SANbox 5600 Series:
Table of Contents

Advertisement

5 – Diagnostics/Troubleshooting
Power-On Self Test Diagnostics

Over Temperature Blink Pattern

An over temperature blink pattern is 5 blinks followed by a two second pause. The
5-blink error pattern indicates that the air temperature inside the switch has
exceeded the failure temperature threshold.
If the Heartbeat LED shows the over temperature blink pattern, do the following:
1.
Inspect the chassis vents. Are the intake and exhaust vents clear?
2.
For a model 5602 switch, inspect the Power Supply Fault LED on both
power supplies; otherwise continue. Is the Power Supply Fault LED
illuminated on either power supply?
3.
For a model 5602 switch, observe the air flow direction from both power
supplies; otherwise continue. Are the flow directions the same?
4.
Consider the ambient air temperature near the switch and clearance around
the switch. Make necessary corrections. If the condition remains, open a
command line window and log on to the switch. Enter the Shutdown
command, then power down the switch. Contact your authorized
maintenance provider.
5-6
2 seconds
Yes - Continue.
No - Remove any debris from fan intake and exhaust if necessary. If
the condition remains, continue.
Yes - Replace the power supply. If the condition remains, continue.
No - Continue.
Yes - Continue.
No - Determine the proper air flow direction for the switch. Replace the
power supply with the incorrect air flow direction with another having
the correct air flow direction. Air flow direction is marked on the power
supply part number label. If the condition remains, continue.
S
59096-06 A