Nordyne P3RD-042K User's Manual And Installation page 7

13 seer single package air conditioner
Table of Contents

Advertisement

CONNECTING
THE RETURN
AND SUPPLY
AIR FLEXIBLE
DUCTS
a.
The supply duct for all units is 12" in diam-
eter. The return duct is 14" diameter for all
air conditioning
units.
b.
The flexible ducts can be connected
to the
corresponding
fittings with the clamps pro-
vided with the ducts. Note: All connections
should be leak tight or a loss in cooling
capacity will result.
c.
The flexible ducts may be cut to the required
length, see instructions
packed with duct.
Keep all ducts as short and straight as pos-
sible. Avoid sharp bends.
d.
Ducts may be spliced with sheet
metal
sleeves and clamps. (See Ducting Instal-
lation Accessories
page 6.)
e.
Once the inner duct is connected
to the
proper
fitting, the insulation
and plastic
sleeve should be pulled over the connection
and clamped.
f.
For homes with multiple supply ducts or for
special applications,
a Y fitting is available
to divide the supply air so it can be ducted
to different areas of the home for more ef-
ficient cooling. Note: TheY fitting should be
insulated for maximum performance.
Model
Wire Color/
Motor
Air Flow
P3RD
Speed Tap
Speed
(0.3 in.WC)
Red
2Ton
Black
Red
2.5 Ton
Black
Red
3Ton
Black
Low
760
High*
1000
Low
760
High*
1000
Low
760
High*
1000
T1
Low
750
T2
Med/Low
1,000
3.5 Ton
Orange / T3
Medium*
1,140
Red / T4
Med/High*
1,300
T5
High
1,350
T1
Low
1,340
Orange / T2
Med/Low*
1,450
4 Ton
Red / T3
Medium*
1,650
T4
Med/High
1,750
T5
High
1,965
T1
Low
1,340
T2
Med/Low
1,450
5 Ton
Orange / T3
Medium*
1,650
Red / T4
Med/High*
1,750
T5
High
1,965
* Factory Setting
Figure 7. Standard Motor Lead Connection
_ Elbow
_""
P-Trap
Figure 8. Drain Trap
Blower
Speed
--
For
optimum
system
performance
and comfort, it may be necessary
to change the factory set speed. See figure 7 for
factory settings. To change the blower speed:
If Standard Motor (2, 2.5 and 3 Ton):
1. Disconnect
all electrical
power
to the
unit and remove the service panel.
2. Place the desired blower speed lead on the
"COM" terminal. Use another wire tie (field
supplied)
to bundle the remaining
motor
leads.
If High Efficiency Motor (3.5, 4, and 5 Ton):
1.
Disconnect
all electrical
power to the unit
and remove the blower panel.
2.
Locate the orange and red wires terminated
to the blower motor. The orange wire controls
cooling operation while the red wire controls
heating operation.
3.
Verify the required speed from the airflow
data found in figure 7. Place appropriate
wire on the appropriate
motor speed tap for
the required airflow point.
Check
all factory
wiring
per the unit wiring
diagram and inspect the factory wiring connec-
tions to be sure none loosened during shipping
or installation.
CAUTION'.
To avoid personal
injury or property
damage,
make certain that the motor
leads cannot come into contact with
any
uninsulated
metal
components
of the unit.