P6sP - 072 / 090 / 120 series, a revision InstallatIon InstructIons single Package Electric Heating / Electric cooling rooftop unit 10T Unit Shown IMPortant attEntIon InstallErs: It is your responsibility to know this product better than your customer. this includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product.
9, 18, 30 and 35KW capacities for long sleeved shirt, and appropriate breathing P6SP models. Use only NORDYNE heater kits listed in protection when working near this insulation. the technical service literature for these units. A single...
Recommended Clearances for Servicibility 60" Minimum Required Clearances to Combustibles 36" 48" 36" 3" 36" Min. Condensate Roof Curb 36" Drain 48" Figure 2. condensate Drain unIt InstallatIon Figure 1. Minimum clearances to Minimum clearance requirements combustibles Units are certified as combination Heating and Cooling equipment for outdoor installation only at the minimum The electric unit is suitable for installation on combustible clearances to combustible materials shown.
Leakage may occur if unit bottom pan is punctured. • If any brand other than a NORDYNE Roof Curb is to be used the frame support must be constructed using Crate Brackets (x4) non-combustible materials.
cIrculatInG aIr suPPlY must be square and level to ensure proper condensate drainage. Unit clearances must be in accordance with WarnInG: those shown in Figure 1 (page 4). unconditioned spaces Do not allow combustion products to enter the All ductwork passing through unconditioned spaces return air ductwork or the circulating air supply.
The unit is shipped ready for downflow duct connections. If voltage wiring requirements. Use NORDYNE 3-Pole Dual horizontal ducts are required, the unit must be converted Circuit Adaptor (P/N-917468 ) for converting to dual supply according to the directions in the conversion kit for both connections.
1. Measure the line voltages unit. Use proper code agency listed conduit and a conduit Example of your 3-phase power connector for connecting the supply wires to the unit and supply where it enters the for obtaining proper grounding. Grounding may also be building and at a location accomplished by using the grounding lug provided in the AB = 451V...
Install the heater kits as directed by the instruction sheet that comes as part of the heater kit. Follow all cautions and warnings as directed. Use only NORDYNE manufactured heater kits.
1. Set the thermostat to above room temperature. 2. Electrical power to the unit is turned on. 2. Verify that the compressor and outdoor fan motor are 3. All safety switches are closed. not energized and the electric heat is energized. 4.
Parts routine Maintenance Proper maintenance is important to achieve optimum Replacement parts are available through all NORDYNE performance from the air conditioner. The ability to properly distributors. When ordering, remember to have the perform maintenance on this equipment requires certain complete Model and Serial number of the unit.
PHYsIcal Data Dimensions shown in inches (mm) Corner D Corner A 16 1/2 (419) 30 1/2 30 1/2 (775) (775) 16 1/2 TOP VieW (419) Corner C Corner B 101 1/2 1 1/4 (2578) (31.8) Control Access Heater Element Access &...
Page 14
PHYsIcal Data - continued Dimensions shown in inches (mm) 15 3/8 conDEnsEr EnD Optional Economizer Hoods Recommended unit Rating disconnect mounting Label location (127) HEat EXcHanGEr EnD 1 3/4 (44) (228) 42 3/4 (1085) 3 1/2 (228) (88) External Power Entry (102) 7 (178) 7 (178)
Page 15
PHYsIcal Data - continued Dimensions shown in inches (mm) Corner D Corner A TOP VieW Corner C Corner B 101 1/2 (406) (2578) Optional Field Wiring Control Access Hail Guard (†)Electric Element Hood Access Blower Access FrOnT VieW Condesate Drain 4 (102) 2 (51) 30 3/4...
Page 16
PHYsIcal Data - continued Dimensions shown in inches (mm) Rating Label Recommended Unit Disconnect Mounting Location HEat EXcHanGEr EnD 4 (102) Airflow Airflow Compressors (x2) conDEnsEr EnD 7 (178) 7 (178) Return Air Opening 5-3/4 (146) 16 1/2 16 1/2 (419) (419) 30 1/2...
ElEctrIcal InForMatIon Model number nominal unit outdoor total High static Indoor Motor unit only P6sP- Voltage compressors Motors unit (see note 4) circuit (see notes 2 & 3) (see note 1) (2) ea. Factory unit Electrical Data: -072C 208 - 230 V 1 ea.
Page 20
100 - 125 921645 -120Da 460 V notE: Nordyne specifically recommends the use of the 917468 Dual Circuit adapter kit for all applications of H5HK 30kW & 35kW Electric Heat Kits. table 3. P6sP Electrical Data - single supply circuits...
Page 21
Figure 13. Wiring Diagram for P6sP-072/090/120 (c/D) series...
Blower Performance tables This equipment is outfitted with a belt driven blower assembly in order to accommodate a large variety of duct configurations and airflow selections. The blower has been factory inspected for proper alignment, operation and rotational direction prior to the drive motor being situated in the shipping position. The blower drive belt is located with these instructions and must be installed by the service technician.
Page 24
P6sP-072(c/D) Factory Standard: 1Hp Down-flow Performance Chart ‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting External Operating Unit @ 230 or Fully Static Turns Turns Turns Turn Turn Turns Turns Turns Turns Turns Turns Turns 460 Volts Closed (in-Wg) Open Open Open ‡...
Page 25
P6sP-072(c/D) Factory Standard: 1.5Hp Horizontal Performance Chart ‡ Indicates Factory Sheave Setting for Pre-configured Units Adjustable Motor Sheave Setting External Operating Unit @ 230 or Fully Static Turns Turn Turn Turns Turns Turns Turns Turns Turns Turns Turns Turns 460 Volts Closed (in-Wg) Open...
Page 26
P6sP-090(c/D)a Factory Standard: 1.5Hp Downflow Performance Chart ‡ Indicates Factory Sheave Setting Adjustable Motor Sheave Setting External Operating Unit @ 230 or Fully Static Turns Turns Turns Turn Turn Turns Turns Turns Turns Turns Turns Turns 460 Volts Closed (in-Wg) Open Open Open...
Page 27
P6sP-090(c/D)a Factory Standard: 1.5Hp Horizontal Performance Chart ‡ Indicates Factory Sheave Setting for Pre-configured Units Adjustable Motor Sheave Setting External Operating Unit @ 230 or Fully Static Turns Turns Turns Turn Turn Turns Turns Turns Turns Turns Turns Turns 460 Volts Closed (in-Wg) Open...
P6sP cHarGInG cHarts, coolInG onlY aPPlIcatIon notEs on tHE usE oF cHarGInG cHarts match the measured liquid temperature to the units chart. This equipments cooling systems contain refrigerant under The measured liquid pressure reading should be within high pressure, always use safe practices when servicing 3% of the value shown for most installations.
Page 31
P6sP cHarGInG cHarts (contInuED) Charging Chart - Cooling Operation - 7.5T P6 Packaged Units * See Application Notes for use Remove refrigerant when above curve Add refrigerant when below curve 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature (F) Figure 16.
InstallatIon / PErForMancE cHEcK lIst InstallEr naME: InstallatIon aDDrEss: CITY _______________________ STATE ________________ CITY ________________________ STATE ________________ UNIT MODEL # ________________________________________ rEFrIGEratIon sYstEM Was unit given 24 hr. warm up period UNIT SERIAL # ________________________________________ for crankcase heaters? Unit Installed Minimum clearances per Figure 1 (page 4)? Ambient Temperature _________________________________ °F ElEctrIcal sYstEM...