Wall Sleeveinstallation - Friedrich WallMaster PTAC Installation & Operation Manual

Ptac packaged terminal air conditioners & heat pumps
Hide thumbs Also See for WallMaster PTAC:
Table of Contents

Advertisement

920-087-02
(9-03)
Wall SleeveInstallation Instructions(PXWS)
NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit includingthe sleeve,chassis and accessories.
If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions
completely before attempting installation.
Figure 5
Typical Wall Sleeve Installation
Lintel to support masonry walls .--_.b_//_
10"
(25.4 cm
Electrical receptacle -
Wall opening
Wall sleeve
/
1
1_ _
/]
41._m)
_\_'[_
--
--
Electrical receptacle
Insulation --
Smooth sideof screw
slip facing into room
For Deep Wall Installation See Section II
The following instructions
apply ONLY to walls less than
13 1/4" in depth.
1.
From inside the building, position the wall sleeve in the opening
and push it through the wall so it protrudes at least 1/4" on the
outside, note Figure 5.
2.
Position the wall sleeve with a slight tilt towards the outside to
facilitate condensate drainage. It should be level side-to-side
and the front should be 1/4 bubble higher than the back. DO
NOT allow any pitch toward the inside.
Electricalshock hazard.
Turn electric power OFF at the fuse box or service panel
before making any electrical connections and ensure a
proper ground connection is made before connecting line
voltage. Failureto do so can result in property damage,
personal injury and/ordeath.