THRU-THE-WALL AIR CONDITIONERS ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service.
NOTE: Units are to be inspected and serviced by qualifi ed service personnel only. Routine maintenance is required annually or semi-annually, depending upon annual usage. Clean the unit air intake fi lter at least every 250 to 300 fan hours of operation or when the unit’s indicator light is on if so equipped.
FRIEDRICH ROOM MODEL NUMBER CODE 1st DIGIT - FUNCTION W = Thru-The-Wall, WallMaster Series 2nd DIGIT - TYPE S = Straight Cool E = Electric Heat Y = Heat Pump 3rd & 4th DIGITS - APPROXIMATE BTU/HR (Cooling) Heating BTU/HR capacity listed in Specifi cations/Performance Data Section...
PERFORMANCE DATA * Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity Calculate the heat loss of the space to be heated. As long as the heat loss does not exceed the resistance heating capacity rating of the unit, the heating performance will be satisfactory. Change-over from heat pump operation to resistance operation on models indicated is automatic at a preset outside ambient temperature of approximately 35°F.
The consumer - through the AHAM Room Air Conditioner Certifi cation Program - can be certain that the AHAM Certifi cation Seal accurately states the unit’s cooling and heating capacity rating, the amperes and the energy effi...
FUNCTIONAL COMPONENTS A. Mechanical components Bellows condensate valve Temperature-sensitive valve that opens up to drain off condensate water when the outside temperature falls below 40°F and closes when the outside temperature reaches 58°F. Plenum assembly Diffuser with directional louvers used to direct the conditioned airfl ow. Blower wheel Attaches to the indoor side of the fan motor shaft and is used for distributing unconditioned, room side air though the heat exchanger and delivering conditioned air into the room.
SYSTEM CONTROL PANEL (“WS” Models) Figure 6: System Control Panel Cool Money Saver ® Speed Mode Fan Only Clock Timer Start Time Hour On/Off Stop Time TESTING THE ELECTRONIC CONTROL CHECKING ROOM TEMPERATURE 1. Check the room temperature at the electronic control pad by pressing at the same time the “FAN SPEED”...
Frost Probe Sensor: Disables compressor at 35 degrees F +/- 3 degrees F Indoor Probe Sensor: Control range is 60 degrees F to 90 degrees F +/- 2 degrees F Indoor temperature will be displayed by pressing: (XQ / WS Units) The Fan Speed button and the Temp Up button.
REFRIGERATION SYSTEM SEQUENCE OF OPERATION A good understanding of the basic operation of the refrigera- tion system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more diffi cult and time consuming, if not (in some cases) entirely impossible.
SEALED REFRIGERATION SYSTEM REPAIRS EQUIPMENT REQUIRED: 1. Voltmeter 2. Ammeter 3. Ohmmeter 4. Vacuum Pump (capable of 200 microns or less vacuum.) 5. Acetylene Welder 6. Electronic Halogen Leak Detector (G.E. Type H-6 or equivalent.) 7. Accurate refrigerant charge measuring device such a.
The introduction of liquid into the low side, without the use of a capillary tube, will cause damage to the discharge valve of the rotary compressor. NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor.
VALVE OPERATING CONDITION Normal Cooling Cool as (2) Normal Heating Cool as (1) Check Electrical circuit and coil Check refrigeration charge Cool Cool, Valve will not as (2) shift from cool to heat. Cool, Cool as (2) Valve will not Cool, shift from cool Cool...
Page 15
COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Low voltage T-stat not set cold enough or inoperative Compressor hums but cuts off on B10 overload Compressor Open or shorted compressor does not run windings Open overload Open capacitor Inoperative system switch Broken, loose or incorrect wiring Problem...
Problem Fuse blown or circuit tripped Power cord not plugged in Unit does not run System switch in "OFF" position Inoperative system switch Loose or disconnected wiring at switch or other components Problem Dirty fi lter Restricted airfl ow Inoperative t-stat Evaporator coil freezes up Short of refrigerant...
Page 17
Instruct customer of waiting period Check voltage with unit operating. Check for other appliances on circuit. Air conditioner should be in separate circuit for proper voltage & fused separately Refer to appropriate wiring diagram...
Page 18
Problem Sublimation: When unconditioned saturated, outside air mixes with conditioned air, condensation forms on the cooler surfaces Water "spitting" into room Downward pitch of installation is too steep Restricted coil or dirty fi lter Problem Insuffi cient air circulation thru area to be air conditioned Oversized unit Excessive moisture...
Page 19
HEAT / COOL ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS Problem Possible Cause Heat anticipator (resistor) shorted (on applicable models) Room temperature uneven Wide differential - partial loss of (Heating cycle) t-stat bulb charge Incorrect wiring Problem Possible Cause Incorrect wiring Defrost control timer motor not advancing (applicable models) Defrost control out of calibration (applicable models)
Page 20
Problem Incorrect wiring Defective solenoid coil Unit cools when heat is called for Reversing valve fails to shift Inoperative system switch Problem Heating capillary tube partially restricted Cooling adequate, Check valve leaking internally but heating insuffi cient Reversing valve failing to shift completely;...
Page 29
“WS” - “WE” - “WY” SERIES SLEEVE PARTS REF. PART NO. 616-036-01 Sleeve Assembly ... 616-032-00 Panel, Weather Inner ... 616-030-01 Grille, Louvered ... 616-033-01 Panel, Weather Outer ... * Not Shown DESCRIPTION CHASSIS PARTS, (Cont.) WS, WE & WY SERIES SLEEVE PARTS APPLICATION...
Page 30
Friedrich Air Conditioning Co. Post Office Box 1540 • San Antonio, Texas 78295-1540 4200 N. Pan Am Expressway • San Antonio, Texas 78218-5212 (210) 357-4400 • FAX (210) 357-4480 www.friedrich.com Printed in the U.S.A. WM-Svc-Prts-06 (7-06)
Need help?
Do you have a question about the WallMaster WE10B33A and is the answer not in the manual?
Questions and answers