Download Print this page

Emerson ControlWave EFM 4710A Instruction Manual page 154

Emerson electronic flow meter instruction manual

Advertisement

Expansion Communications Module:
COM4, COM5, COM6 & COM7 on 1
COM8, COM9, COM10 and COM11 on 2
COM4/8 -
Port 1: ECOM Bd. J1, PC/AT 9-Pin Male D-Sub - Both RS-232
COM5/9 -
Port 2: ECOM Bd. J2, PC/AT 9-Pin Male D-Sub - Both RS-485
COM6/10 - Port 3: ECOM Bd. Piggy-back Radio Module (FreeWave or MDS TransNet
Spread Spectrum Modem) Antenna connector provided (Optional)
COM7/11 - Port 4: ECOM Bd. Piggy-back Modem Module (Multitech 56KB PL/PSTN
Modem) RJ-11 connector provided (Optional)
Communication Ports COM1, COM2, COM3, COM4, COM5, COM8 and COM9 support
serial asynchronous operation. Communication Ports COM1, COM2, COM4 and COM5
support RS-232 while COM3, COM5 and COM9 support RS-485 operation. Com-
munication Ports COM4/8, COM5/9, COM6/10 and COM7/11 reside on optional
Expansion Communications Modules (ECOM1/2). ECOM1 must reside in Base Chassis
Backplane Slot #3 while ECOM2 must reside in Base Chassis Backplane Slot #4. ECOM
Modules have one RS-232 Port and one RS-485 Port. Additionally, an ECOM Module
may optionally contain a 56Kbaud PSTN Modem and/or a Spread Spectrum Modem
(Radio). Any communication port can be configured for local communications, i.e.,
connected to a PC loaded with ControlWave Designer and OpenBSI software. The pin
labels for the 9-pin, RS-232/485 interface are provided in Table C-4.
Table C-4 - RS-232 Ports COM1/2/4/8 and RS-485 Ports COM3/5/9
Pin
Signal
#
RS-232
1
DCD
Data Carrier Detect Input
2
RXD
Receive Data Input
3
TXD
Transmit Data Output
4
DTR
Data Terminal Ready Output
5
GND
Signal/Power Ground
6
DSR
Data Set Ready Input
7
RTS
Request To Send Output
8
CTS
Clear To Send Input
9
N/A
* ISOGND on Isolated RS-485 Ports Only!
Remove any Expansion Communication Module and configure its Jumpers as required
(see Figures C-4A & C-4B). Install each Expansion Comm. Modules into the appropriate
ControlWave EFM Base Housing Communication I/O Slot. Expansion Comm. Modules
may reside in ControlWave EFM Base Housing Slots #3 and #4 ONLY (1
resides in Slot #3, 2
reside in Expansion Housings.
Spread Spectrum Modem Port
An optional Spread Spectrum Modem (Radio) is available on each Expansion Com-
munications Module (mounted piggy-back) and is assigned port status as follows: COM6 for
ECOM1 and COM10 for ECOM2. There are two unique radios offered. These radios will
only communicate with their own brand of radio, i.e., FreeWave radios are not compatible
with MDS radios. DTE/DCE serial data can be clocked into (transmit) or out of (receive) the
radio at a rate up to 115.2kHz.
C-6 / Appendix C - Hardware Installation Guide
ECOM Bd., - assigned to Base Housing Slot #3
st
nd
Connector Pin Assignments
Description:
RS-232 Signals
ECOM resides in Slot #4). Expansion Comm. Modules may not
nd
ECOM Bd., assigned to Base Housing Slot #4
Signal
RS-485
N/A
RXD-
Receive Data - Input
TXD-
Transmit Data - Output
TXD+
Transmit Data + Output
GND/ISOGND*
Ground/Isolated Ground*
RXD+
Receive Data + Input
N/A
N/A
N/A
Description:
RS-485 Signals
ECOM
st
CI-ControlWave EFM

Advertisement

loading

This manual is also suitable for:

Controlwave efm fgr09csuBristol controlwave efm